Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: UNITED FACILITIES, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of UNITED FACILITIES, INC. in 603 NORTH MAIN STREET, EAST PEORIA, IL 61611 (NAICS 493190). OSHA activity number 348409236.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch United Facilities, INC. — free Get an email when a new federal OSHA severe-injury report for United Facilities, INC. is published. One employer, no account, unsubscribe in one click.
Site address
603 NORTH MAIN STREET
City
EAST PEORIA
State
IL
ZIP
61611
Mailing
603 NORTH MAIN STREET, EAST PEORIA, IL 61611
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493190
Employees
12
Ownership type
A

7 citations on file for this inspection.

1910.22 A02

Other-than-serious Gravity 1 1 instance 22 exposed
Issued
Sep 19, 2025
Penalty
Initial $6,029 · Current $0 Reduced
29 CFR 1910.22(a)(2): The employer did not ensure that the  floor of each workroom is maintained in a clean and, to the extent feasible, in a dry condition:  On or about July 31, 2025, employees were exposed to slip hazards from a wet floor in the restroom and the employer failed to ensure the toilet was properly maintained to prevent water from splashing on the floor when flushed.
Recent events (2)
  • — I (O) $0
  • — Z (S) $6029

1910.37 B05

Serious Gravity 1 1 instance 4 exposed
Issued
Sep 19, 2025
Penalty
Initial $6,029 · Current $3,200 Reduced
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):  On or about July 31, 2025, employees working in Building B were exposed to smoke inhalation and minor burns in the event of a fire and the employer did not ensure that the doors that could be mistaken for exits were marked "Not an Exit."
Recent events (2)
  • — I (S) $3200
  • — Z (S) $6029

1910.141 C01 I

Serious Gravity 1 1 instance 22 exposed
Issued
Sep 19, 2025
Penalty
Initial $6,029 · Current $3,200 Reduced
29 CFR 1910.141(c)(1)(i): Toilet facilities were not provided in accordance with TABLE J-1 of this Section:   On or about July 31, 2025, the employer did not ensure that the appropriate number of toilet facilities was provided for the number of employees working at the location.
Recent events (2)
  • — I (S) $3200
  • — Z (S) $6029

1910.303 B01

Serious Gravity 5 3 instances 4 exposed
Issued
Sep 19, 2025
Abate by
Oct 21, 2025
Penalty
Initial $8,038 · Current $3,600 Reduced
29 CFR 1910.303(b)(1): Examination. Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees, in that the employer did not ensure the safety of the equipment pursuant to the considerations in sections (i) through (viii) of 29 CR 1910.303(b)(1):  a)  On or about July 31, 2025, employees using the shrink wrapping equipment in Building  B were exposed to electrical hazards and the employer had not examined the equipment to ensure that extension cords that were series connected (daisy chained) were used in accordance with their label and listing.  b) On or about July 31, 2025, employees working near the NW corner of Building B were exposed to electrical hazards and the employer had not examined the cord(s) to ensure that flexible cords were only used in continuous lengths.  c) On or about July 31, 2025, employees working in the NW corner of  Building B were exposed to electrical hazards and the employer had not examined the equipment to ensure that extension cords and relocatable power taps (RPT) that were series connected (daisy chained) were used in accordance with their label and listing.
Recent events (2)
  • — I (S) $3600
  • — Z (S) $8038

1910.303 B02

Serious Gravity 5 2 instances 4 exposed
Issued
Sep 19, 2025
Abate by
Oct 21, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a)  On or about July 31, 2025, employees using the shrink wrapping equipment in Building  B were exposed to electrical hazards and the employer had not ensured that extension cords were used in accordance with their label and listing.  b) On or about July 31, 2025, employees working near the NW corner of Building B were exposed to electrical hazards and the employer had not ensured that a relocatable power tap (RPT) was used in accordance with its label and listing.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 4 exposed
Issued
Sep 19, 2025
Abate by
Oct 21, 2025
Penalty
Initial $8,038 · Current $0 Reduced
29 CFR 1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  On or about July 31, 2025, employees working with the pallet/shrink wrapper in Building B were exposed to electrical hazards and the employer had not ensured that the flexible cords were not used in lieu of fixed wiring.
Recent events (2)
  • — I (S) $0
  • — Z (S) $8038

1910.305 G02 II

Serious Gravity 5 1 instance 4 exposed
Issued
Sep 19, 2025
Abate by
Sep 30, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(ii):Flexible cords were not used only in continuous lengths without splice or tap:  On or about July 31, 2025, employees working near the NW corner of Building B were exposed to electrical hazards and the employer had ensured that flexible cords were only used in continuous lengths without a splice.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View United Facilities, INC.'s full OSHA safety record →