Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DEPT. OF AGRICULTURE - NRCS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of DEPT. OF AGRICULTURE - NRCS in 528 91ST AVE NE, SUITE C, LAKE STEVENS, WA 98258 (NAICS 924110). OSHA activity number 348444373.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Dept. of Agriculture - Nrcs — free Get an email when a new federal OSHA severe-injury report for Dept. of Agriculture - Nrcs is published. One employer, no account, unsubscribe in one click.
Site address
528 91ST AVE NE, SUITE C
City
LAKE STEVENS
State
WA
ZIP
98258
Mailing
528 91ST AVE NE, SUITE C, LAKE STEVENS, WA 98258
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924110
Employees
3
Ownership type
D

1 citation on file for this inspection.

1910.304 B04 II B

Serious Gravity 5 1 instance 4 exposed
Issued
Nov 21, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.304(b)(4)(ii)(B):Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4:  A)    Office Break Room -  On or about August 14, 2025, employees were exposed to electrical and fire hazards because a relocatable power strip with 15 amp receptacles, plugged into a 15 amp wall outlet, connected to a 20 amp branch circuit were overloaded. There was a 13.3 amp microwave oven, 9.7 amp toaster oven, and 7.5 amp coffee maker, drawing 30 amps of current through the outlet and power strip.
Recent events (1)
  • — Z (S) $0

View Dept. of Agriculture - Nrcs's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348444373.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.