Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: HANWHA Q CELLS USA CORP.

Programmed Related inspection · Safety discipline

On , OSHA opened a programmed Related safety inspection of HANWHA Q CELLS USA CORP. in 10490 CR 90, SEVERANCE, CO 80524 (NAICS 221114). OSHA activity number 348450768.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hanwha Q Cells USA Corp. — free Get an email when a new federal OSHA severe-injury report for Hanwha Q Cells USA Corp. is published. One employer, no account, unsubscribe in one click.
Site address
10490 CR 90
City
SEVERANCE
State
CO
ZIP
80524
Mailing
300 SPECTRUM CENTER DR STE 500, IRVINE, CA 92618
Inspection type
Programmed Related (J)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221114
Employees
20
Ownership type
A

3 citations on file for this inspection.

1910.269 D02 III

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 30, 2026
Abate by
Jun 10, 2026
Penalty
Initial $16,550 · Current $16,550
29 CFR  1910.269(d)(2)(iii): Procedures shall be developed, documented, and used for the control of potentially hazardous energy covered by paragraph (d) of this section:  On or about August 18, 2025, the host employer failed to ensure that procedures for the control of hazardous energy were strictly adhered to.  Technicians (both employees of the company and subcontracted employees) were not protected from hazards created by arc flash/arc blast in that technicians engaged in the group lockout of the PCS 025 (SG4400UD-MV-US, Serial #T2520600152) did not verify that electrical energy had been de-energized, and isolated, prior to commencing maintenance activities.
Recent events (3)
  • — F (S) $16550
  • — C (S) $16550
  • — Z (S) $16550

1910.269 D06 VII

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Jan 30, 2026
Abate by
Feb 26, 2026
Penalty
Initial $16,550 · Current $0 Reduced
29 CFR  1910.269(d)(6)(vii): Before starting work on machines or equipment that have been locked out or tagged out, the authorized employee shall verify that isolation and deenergizing of the machine or equipment have been accomplished. If normally energized parts will be exposed to contact by an employee while the machine or equipment is deenergized, a test shall be performed to ensure that these parts are deenergized:  a) On or about August 18, 2025, the controlling employer did not ensure employees and subcontracted employees were protected from arc flash explosion hazards.  Commissioning technicians engaged in the group lockout of the PCS 025 (SG4400UD-MV-US, Serial #T2520600152) with subcontracted employees, did not verify that electrical energy had been de-energized, and isolated, prior to commencing maintenance activities.  This condition exposed employees and subcontracted employees to arc flash explosion hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $16550
  • — Z (S) $16550

1910.269 D08 III

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Jan 30, 2026
Abate by
Feb 26, 2026
Penalty
Initial $16,550 · Current $0 Reduced
29 CFR  1910.269(d)(8)(iii): Procedures shall be used during shift or personnel changes to ensure the continuity of lockout or tagout protection, including provision for the orderly transfer of lockout or tagout device protection between off-going and on-coming employees, to minimize their exposure to hazards from the unexpected energizing or start-up of the machine or equipment or from the release of stored energy:   a) On or about August 18, 2025, the controlling employer did not ensure the authorized employee responsible for the lock-out/tag-out of the PCS 025 (SG4400UD-MV-US, Serial #T2520600152) requested removal or transfer of a lock-out tag-out device prior to leaving the site. This condition exposed employees to the hazard of un-expected energization of the equipment during maintenance activities.
Recent events (3)
  • — F (S) $0
  • — C (S) $16550
  • — Z (S) $16550

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348450768.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.