Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: BLOUNT FINE FOOD

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of BLOUNT FINE FOOD in 630 CURRAND ROAD, FALL RIVER, MA 02720 (NAICS 424460). OSHA activity number 348451121.

Watch Blount Fine Food — free Get an email when a new federal OSHA severe-injury report for Blount Fine Food is published. One employer, no account, unsubscribe in one click.
Establishment
BLOUNT FINE FOOD
Site address
630 CURRAND ROAD
City
FALL RIVER
State
MA
ZIP
02720
Mailing
630 CURRAND ROAD, FALL RIVER, MA 02720
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424460
Employees
1025
Ownership type
A

6 citations on file for this inspection.

1910.119 J02

Other-than-serious Gravity 5 1 instance 300 exposed
Issued
Abate by
Penalty
Initial $14188.00 · Current $6250.00 Reduced
29 CFR  1910.119(j)(2): The employer did not develop and implement written procedures to maintain the on-going integrity of process equipment.   Location: Worksite, ammonia engine room.  The employer did not develop and implement a written procedures for inspecting and servicing compressor drive shaft seals.
Recent events (2)
  • — I (O) $6250
  • — Z (S) $14188

1910.119 J04 III

Other-than-serious Gravity 5 2 instances 300 exposed
Issued
Abate by
Penalty
Initial $14188.00 · Current $6250.00 Reduced
29 CFR  1910.119(j)(4)(iii):The frequency of inspections and tests of process equipment shall be consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience.  Location: Ammonia refrigeration engine room  The employer did not ensure that ammonia gas sensors in the facility had not been calibrated according to the manufacture's six month requirement.
Recent events (2)
  • — I (O) $6250
  • — Z (S) $14188

1910.119 J05

Other-than-serious Gravity 5 1 instance 300 exposed
Issued
Abate by
Penalty
Initial $14188.00 · Current $6250.00 Reduced
29 CFR  1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information in paragraph (d) of this section) before further use or in a safe and timely manner when necessary means were taken to assure safe operation:   Location: Ammonia refrigeration engine room.   The employer did not address issues such as excessive corrosion on valves and piping in the ammonia refrigeration system.
Recent events (2)
  • — I (O) $6250
  • — Z (S) $14188

1910.119 L01

Other-than-serious Gravity 5 1 instance 300 exposed
Issued
Abate by
Penalty
Initial $14188.00 · Current $6250.00 Reduced
29 CFR  1910.119(l)(1):The employer did not establish written procedures to manage changes to process chemicals, technology, equipment, and procedures, and changes to facilities that affect a covered process.  Location: Ammonia refrigeration engine room.  The employer did not develop a Management of Change (MOC) to  address a broken motor disconnect switch on RC-08 resulting the use of a 480 volt circuit breaker, located in the switch gear room, to switch power.
Recent events (2)
  • — I (O) $6250
  • — Z (S) $14188

1910.119 F01

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $165514.00 · Current $125000.00 Reduced
29 CFR  1910.119(f)(1): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with the process safety information:   Location: Ammonia refrigeration system engine room.   The employer did not develop and implement temporary written operating procedures addressing a broken motor disconnect switch on RC-08, resulting in the use of a 480 volt circuit breaker located in the switch gear room to switch power.
Recent events (2)
  • — I (S) $125000
  • — Z (W) $165514

1910.305 J04 II

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(j)(4)(ii): As it applies to motors, motor circuits and controllers; a disconnecting means for the controller was not located within sight of the controller location ( i.e. that one piece of equipment shall be within sight of another piece of equipment, the piece of equipment shall be visible and not more than 50 feet from the other).     location; Ammonia refrigeration engine room  On or about August 20, 2025, and at times prior, the employer did not have a means of disconnecting power to the RC-8 drive motor that was in sight and within 50 feet.