Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: VIANT COLLEGEVILLE, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of VIANT COLLEGEVILLE, LLC in 200 WEST 7TH AVENUE, COLLEGEVILLE, PA 19426 (NAICS 423450). OSHA activity number 348456765.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Viant Collegeville, LLC — free Get an email when a new federal OSHA severe-injury report for Viant Collegeville, LLC is published. One employer, no account, unsubscribe in one click.
Site address
200 WEST 7TH AVENUE
City
COLLEGEVILLE
State
PA
ZIP
19426
Mailing
200 WEST 7TH AVENUE, COLLEGEVILLE, PA 19426
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423450
Employees
85
Ownership type
A

4 citations on file for this inspection.

1910.305 G01 III

Serious Gravity 1 3 instances 1 exposed
Issued
Feb 12, 2026
Penalty
Initial $8,512 · Current $6,384 Reduced
29 CFR  1910.305(g)(1)(iii):Flexible cords and cables were used for purposes prohibited by subparagraphs (A) through (E) of this paragraph:  a)  200 West 7th Ave, Collegeville, ECM and Fab area rear exit door - Employees are performing work tasks in a shop area that contains flexible cords used for permanent wiring.  Energized extension cord secured to building's structure, over a pedestrian walkway, powering a vending machine on the other side.  b)  200 West 7th Ave, Collegeville, ECM and Fab area rear exit door - Employees are performing work tasks in a shop area with flexible cords utilized for permanent wiring.  Energized extension cord is run from a hallway between a door and frame, into another room to power a scale.  c)  200 West 7th Ave, Collegeville, ECM and Fab area - Employees are performing work tasks in a shop area with flexible cords utilized for permanent wiring.  An energized extension cord is secured to overhead building members and powers a machine that dispenses personal protective equipment.
Recent events (2)
  • — I (S) $6384
  • — Z (S) $8512

1910.333 C02

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 12, 2026
Abate by
Mar 4, 2026
Penalty
Initial $14,188 · Current $10,641 Reduced
29 CFR  1910.333(c)(2): The employer did not ensure that qualified persons were capable of working safely on energized circuits and were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools:  a)  200 West 7th Ave Collegeville, Shop Area - Maintenance employees are regularly assigned to perform work tasks involving energized parts and circuitry ranging from 50 to 480 volts.  The employer has not provided arc flash training to the employees performing this work.
Recent events (2)
  • — I (S) $10641
  • — Z (S) $14188

1910.157 G04

Other-than-serious 1 instance 1 exposed
Issued
Feb 12, 2026
Abate by
Mar 4, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.157(g)(4):Employees who have been designated to use fire fighting equipment as a part of the emergency action plan were not provided training in the use of appropriate equipment upon initial assignment and at least annually thereafter:  a)  200 West 7th Ave Collegeville - Employees are expected to utilize portable extinguishers in the event of a fire.  Employee training has lapsed beyond the one year period.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 I A

Other-than-serious 1 instance 1 exposed
Issued
Feb 12, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(i)(A):For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening whwere they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:  a)  200 W. 7th Ave Collegeville -  Employees are performing work tasks in a shop area.  An electrical disconnect was obstructed so that it could not be readily accessed for operation or examination.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Viant Collegeville, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348456765.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.