Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: VETCHECK - WESLEY CHAPEL LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of VETCHECK - WESLEY CHAPEL LLC in 4424 FRIENDLY WAY SUITE 130, WESLEY CHAPEL, FL 33543 (NAICS 541940). OSHA activity number 348499153.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Vetcheck - Wesley Chapel LLC for free Get an email when a new federal OSHA severe-injury report for Vetcheck - Wesley Chapel LLC is published. One employer, no account, unsubscribe in one click.
Site address
4424 FRIENDLY WAY SUITE 130
City
WESLEY CHAPEL
State
FL
ZIP
33543
Mailing
12080 SHADY KNOLL DRIVE, FISHERS, IN 46037
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541940
Employees
6
Ownership type
Private (A)

2 citations on file for this inspection.

1910.303 G01 I

Serious Gravity 1 1 instance 4 exposed
Issued
Dec 4, 2025
Abate by
Dec 31, 2025
Penalty
Initial $2,979 · Current $1,787 Reduced
29 CFR  1910.303(g)(1)(i):The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1:  (a) In the X-Ray Room, located at 4424 Friendly Way, Wesley Chapel, FL 33543, on or about 9/11/2025, the employer exposed employees to electrical hazards, in that the 125 kV InnoVet X-Ray machine was placed directly in front of the disconnect, preventing its access by employees.
Recent events (2)
  • · I (S) $1787.4
  • · Z (S) $2979

1910.1096 D02

Serious Gravity 1 1 instance 3 exposed
Issued
Dec 4, 2025
Penalty
Initial $2,979 · Current $1,787 Reduced
29 CFR  1910.1096(d)(2):Appropriate personnel monitoring or equipment such as film badges, pocket chambers, pocket dosimeters of film rings were not supplied to or required to be used by employee(s) as described in 29 CFR 1910.1096(d)(2)(i),(d)(2)(ii) and (d)(2)(iii):  (a) In the X-Ray Room, located at 4424 Friendly Way, Wesley Chapel, FL 33543, on or about 9/11/2025, the employer exposed employees to radiation hazards, in that employees who were performing X-Rays with an InnoVet X-Ray machine were not provided with an ionizing radiation monitoring device
Recent events (2)
  • · I (S) $1787.4
  • · Z (S) $2979

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 348499153.