OSHA Inspection: RESA POWER, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of RESA POWER, LLC in 9800 SOUTH CASS AVENUE BUILDING 240, LEMONT, IL 60439 (NAICS 811412). OSHA activity number 348509258.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Resa Power, LLC — free Get an email when a new federal OSHA severe-injury report for Resa Power, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
RESA POWER, LLC
Site address
9800 SOUTH CASS AVENUE BUILDING 240
City
LEMONT
State
IL
ZIP
60439
Mailing
550 W. FRONTAGE RD., NORTHFIELD, IL 60093
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
811412
Employees
14
Ownership type
A

3 citations on file for this inspection.

1910.333 B02

Serious Gravity 10 1 instance 3 exposed
Issued
Feb 13, 2026
Abate by
Mar 9, 2026
Penalty
Initial $16,550 · Current $16,550
29 CFR  1910.333(b)(2): "Lockout and Tagging." While any employee is exposed to contact with parts of fixed electric equipment or circuits which have been deenergized, the circuits energizing the parts shall be locked out or tagged or both in accordance with the requirements of this paragraph.   On or about September 15, 2025,  in Theory and Computer Sciences (TCS) Building #240 at Argonne National Laboratory, the employer did not ensure that locks and/or tags were applied to the electrical feed(s) for Transformer 15A prior to allowing employees to begin work.  Employees were exposed to electrical shock hazards while replacing the bushings of Transformer 15A.  Abatement certification is required of this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
  • — C (S) $16550
  • — Z (S) $16550

1910.334 C03

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 13, 2026
Abate by
Mar 9, 2026
Penalty
Initial $16,550 · Current $16,550
29 CFR  1910.334(c)(3): Rating of equipment. Test instruments and equipment and their accessories shall be rated for the circuits and equipment to which they will be connected and shall be designed for the environment in which they will be used.  On or about September 15, 2025,  in Theory and Computer Sciences (TCS) Building #240 at Argonne National Laboratory, the employer did not ensure electrical circuits were tested with rated equipment.  Employees were testing the bushings of Transformer 15A using a multi-meter, rated for a maximum of 1,000 volts, on an energized component operating at a nominal voltage of 13,200 volts.  Abatement certification is required of this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
  • — C (S) $16550
  • — Z (S) $16550

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 13, 2026
Abate by
Mar 9, 2026
Penalty
Initial $16,550 · Current $16,550
29 CFR  1910.335(a)(1)(i):Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.   On or about September 15, 2025,  in Theory and Computer Sciences (TCS) Building #240 at Argonne National Laboratory, the employer did not ensure electrical protective equipment was used at Transformer 15A.  An employee received an electrical shock while checking voltage inside the cabinet without electrical protective equipment.  Abatement certification is required of this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
  • — C (S) $16550
  • — Z (S) $16550

View Resa Power, LLC's full OSHA safety record →