BENTON, ME —
OSHA Inspection: LONGROAD ENERGY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of LONGROAD ENERGY in 1120 UNITY ROAD, BENTON, ME 04901 (NAICS 221114). OSHA activity number 348557281.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LONGROAD ENERGY
- Site address
- 1120 UNITY ROAD
- City
- BENTON
- State
- ME
- ZIP
- 04901
- Mailing
- 125 HIGH STREET SUITE 1705, BOSTON, MA 02110
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221114
- Employees
- 262
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.132 D01 I
- Issued
- Mar 10, 2026
- Penalty
- Initial $16,550 · Current $16,240 Reduced
General-duty citation text
29 CFR 1910.132(d)(1)(i): When the employer had assessed the workplace hazard(s) and determined that hazard(s) were present, the employer did not select and/or use the types of personal protective equipment that would protect the affected employee from the hazards present: Three Corners Solar Field - Employer failed to ensure employees used the proper face protection, as listed in their hazard assessment and live electrical work permit, when they negated need for face shield due to low arc hazard but did not further assess possible other hazards that shield was being used to protect employees from, resulting in an serious cross body electrical shock by entry through an employee's right cheek and exit out the left employee's hand.
Recent events (2)
- — I (S) $16240
- — Z (S) $16550
1910.269 L03 III
- Issued
- Mar 10, 2026
- Abate by
- Apr 24, 2026
- Penalty
- Initial $16,550 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(l)(3)(iii): The employer did not ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless: [A] The employee is insulated from the energized part (rubber insulating gloves or rubber insulating gloves and sleeves worn in accordance with paragraph (l)(4) of this section constitutes insulation of the employee from the energized part upon which the employee is working provided that the employee has control of the part in a manner sufficient to prevent exposure to uninsulated portions of the employee's body), or [B] The energized part is insulated from the employee and from any other conductive object at a different potential, or [C] The employee is insulated from any other exposed conductive object in accordance with the requirements for live-line bare hand work in paragraph (q)(3) of this section: Three Corners Solar Field - Employer failed to ensure that employees were at least 1 inch from energized parts between 301 and 5,000 volts when replacing solar modules (panels) as an employee contacted an MC4 connector with their cheek and sustained a cross body electric shock rendering the employee briefly unconscious and requiring hospitalization.
Recent events (2)
- — I (S) $0
- — Z (S) $16550
More inspections in this industry (NAICS 221114)
More inspections in ME
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348557281.