Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: SOUTHEAST POWER CORPORATION WESTERN

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of SOUTHEAST POWER CORPORATION WESTERN in TOWER 130 NEAR 302 EAST KRUEGER STREET, MARION, TX 78124 (NAICS 221115). OSHA activity number 348569229.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Southeast Power Corporation Western for free Get an email when a new federal OSHA severe-injury report for Southeast Power Corporation Western is published. One employer, no account, unsubscribe in one click.
Site address
TOWER 130 NEAR 302 EAST KRUEGER STREET
City
MARION
State
TX
ZIP
78124
Mailing
851 S DUNLAWTON AVE STE 302, PORT ORANGE, FL 32127
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Last modified
Data loaded
NAICS code
221115
Employees
1
Ownership type
Private (A)

3 citations on file for this inspection.

1926.960 B01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 23, 2026
Abate by
May 19, 2026
Penalty
Initial $11,585 · Current $11,585
29 CFR 1926.960(b)(1)(i): Unqualified employees worked on and/or with exposed energized lines and/or parts of equipment.  On or about October 23, 2025,  linemen were performing work on energized lines and/or parts of equipment without being qualified.
Recent events (2)
  • · C (S) $11585
  • · Z (S) $11585

1926.960 C01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 23, 2026
Abate by
May 19, 2026
Penalty
Initial $11,585 · Current $11,585
29 CFR 1926.960(c)(1)(i): The employer did not establish minimum approach distances no less than the distances computed by Table V-2 for AC systems or Table V-7 for DC systems.   On or about October 23, 2025, a lineman was performing work on energized lines and/or parts of equipment without the minimum approach distance being established.
Recent events (2)
  • · C (S) $11585
  • · Z (S) $11585

1926.960 C01 II

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 23, 2026
Abate by
May 19, 2026
Penalty
Initial $11,585 · Current $11,585
29 CFR 1926.960(c)(1)(ii): The employer did not determine the maximum anticipated per-unit transient overvoltage, phase-to-ground, through an engineering analysis or assume a maximum anticipated per-unit transient overvoltage, phase-to-ground, in accordance with Table V-8.    On or about October 23, 2025, an engineering analysis was not performed prior to the beginning of work on or near energized powerlines.
Recent events (2)
  • · C (S) $11585
  • · Z (S) $11585

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 348569229.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.