Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PMG PENNSYLVANIA CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PMG PENNSYLVANIA CORPORATION in 187 ENTERPRISE DRIVE, PHILIPSBURG, PA 16866 (NAICS 332117). OSHA activity number 348609314.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch PMG Pennsylvania Corporation — free Get an email when a new federal OSHA severe-injury report for PMG Pennsylvania Corporation is published. One employer, no account, unsubscribe in one click.
Site address
187 ENTERPRISE DRIVE
City
PHILIPSBURG
State
PA
ZIP
16866
Mailing
187 ENTERPRISE DRIVE C/O MORGAN GARDNER, PHILIPSBURG, PA 16866
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332117
Employees
124
Ownership type
A

4 citations on file for this inspection.

1910.22 A01

Serious Gravity 5 1 instance 66 exposed
Issued
Feb 20, 2026
Abate by
May 1, 2026
Penalty
Initial $7,235 · Current $7,000 Reduced
29 CFR  1910.22(a)(1): Places of employment were not kept clean:  (a) PMG Pennsylvania Corporation, 187 Enterprise Drive, Philipsburg, Pennsylvania - Combustible powdered metal dust had accumulated on ceiling level surfaces, including ductwork, exposing employees to a fire hazard, on or about November 20, 2025.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and state employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $7235

1910.147 C06 I

Other-than-serious Gravity 5 1 instance 10 exposed
Issued
Feb 20, 2026
Abate by
May 1, 2026
Penalty
Initial $7,235 · Current $0 Reduced
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:  (a) PMG Pennsylvania Corporation, 187 Enterprise Drive, Philipsburg, Pennsylvania - The employer did not conduct an annual periodic inspection of lockout/tagout procedures, exposing employees to machinery hazards such as caught in, entanglement, and struck by, on or about November 20, 2025.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and state employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $0
  • — Z (S) $7235

1910.219 C04 I

Serious Gravity 1 1 instance 3 exposed
Issued
Feb 20, 2026
Abate by
May 1, 2026
Penalty
Initial $5,426 · Current $5,000 Reduced
29 CFR 1910.219(c)(4)(i): Unguarded projecting shaft ends did not present a smooth edge and end and projected more than one half the diameter of the shaft:  (a) Furnace 4 - The horizontal shaft end, 41 inches above the floor, on the belt conveyor where the belt dumps excess powder off parts before Furnace 4, did not present a smooth edge due to having set screws, and this shaft end did not have guarding, on or about November 20, 2025.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and state employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $5000
  • — Z (S) $5426

1910.303 B02

Serious Gravity 1 1 instance 3 exposed
Issued
Feb 20, 2026
Abate by
May 1, 2026
Penalty
Initial $5,426 · Current $5,000 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) Presto Power Stak Lift Parking Area - A two-receptacle metal knockout box, installed as a pendant on a flexible cord, supplied power to cord and plug connected equipment, including the charging cord for the Presto Power Stak Lift.  This use did not follow the listing, labeling, and certification for receptacles, which require using non-metallic enclosures and cover plates for pendent receptacles, on or about November 20, 2025.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and state employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $5000
  • — Z (S) $5426

View PMG Pennsylvania Corporation's full OSHA safety record →