Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: 24M TECHNOLOGIES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of 24M TECHNOLOGIES, INC. in 130 BROOKLINE STREET, CAMBRIDGE, MA 02139 (NAICS 335912). OSHA activity number 348614900.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch 24M Technologies, INC. — free Get an email when a new federal OSHA severe-injury report for 24M Technologies, INC. is published. One employer, no account, unsubscribe in one click.
Site address
130 BROOKLINE STREET
City
CAMBRIDGE
State
MA
ZIP
02139
Mailing
130 BROOKLINE STREET, CAMBRIDGE, MA 02139
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
335912
Employees
80
Ownership type
A

2 citations on file for this inspection.

1910.106 D04 I

Serious Gravity 5 1 instance 80 exposed
Issued
Jan 22, 2026
Abate by
Apr 30, 2026
Penalty
Initial $8,511 · Current $8,511
29 CFR  1910.106(d)(4)(i):Inside flammable or combustible liquid storage room(s) were not constructed to meet the required fire-resistive rating as specified in NFPA 251-1969:  Location: Warehouse B, Room 141  a) On or about 11/25/25, the employer did not ensure that a flammable or combustible liquid storage room was constructed to meet NFPA 251-1969, in that the floor was not provided with a liquid-tight sill or ramp. Both category 2 and category 3 flammable materials were stored within the room.
Recent events (3)
  • — A (S) $8511
  • — I (S) $4000
  • — Z (S) $8511

1910.106 D04 III

Serious Gravity 5 1 instance 80 exposed
Issued
Jan 22, 2026
Abate by
Apr 30, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.106(d)(4)(iii): Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), was not approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Category 3 flammable liquids with a flashpoint at or above 100 °F (37.8 °C) and Category 4 flammable liquids, was not approved for general use.  Location: Warehouse B, Room 141  a) On or about 11/25/25, the employer did not ensure that electrical equipment installed in a flammable or combustible liquid storage room was approved for inside storage rooms with Category 2 and 3 flammable liquids. Both category 2 flammable liquids and category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C) were found stored in a storage room that had general use wiring.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348614900.