Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: UNIVERSITY OF DAYTON

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of UNIVERSITY OF DAYTON in 300 COLLEGE PARK, DAYTON, OH 45469 (NAICS 611310). OSHA activity number 348615857.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch University of Dayton — free Get an email when a new federal OSHA severe-injury report for University of Dayton is published. One employer, no account, unsubscribe in one click.
Site address
300 COLLEGE PARK
City
DAYTON
State
OH
ZIP
45469
Mailing
300 COLLEGE PARK, DAYTON, OH 45469
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
611310
Employees
3700
Ownership type
A

2 citations on file for this inspection.

1910.333 B02

Serious Gravity 10 1 instance 3 exposed
Issued
Dec 10, 2025
Abate by
Jan 29, 2026
Penalty
Initial $16,550 · Current $8,275 Reduced
29 CFR  1910.333(b)(2):"Lockout and Tagging." While any employee is exposed to contact with parts of fixed electric equipment or circuits which have been deenergized, the circuits energizing the parts shall be locked out or tagged or both in accordance with the requirements of this paragraph. The requirements shall be followed in the order in which they are presented (i.e., paragraph (b)(2)(i) first, then paragraph (b)(2)(ii), etc.). Note 1: As used in this section, fixed equipment refers to equipment fastened in place or connected by permanent wiring methods. Note 2: Lockout and tagging procedures that comply with paragraphs (c) through (f) of 1910.147 will also be deemed to comply with paragraph (b)(2) of this section provided that: [1] The procedures address the electrical safety hazards covered by this Subpart; and [2] The procedures also incorporate the requirements of paragraphs (b)(2)(iii)(D) and (b)(2)(iv)(B) of this section.  -	1910.333(b)(2)(ii)(C) -	Stored electric energy which might endanger personnel shall be released. Capacitors shall be discharged and high capacitance elements shall be short-circuited and grounded, if the stored electric energy might endanger personnel. -	1910.333(b)(2)(iii)(A) -	A lock and a tag shall be placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed, except as provided in paragraphs (b)(2)(iii)(C) and (b)(2)(iii)(E) of this section. The lock shall be attached so as to prevent persons from operating the disconnecting means unless they resort to undue force or the use of tools. -	1910.333(b)(2)(iv) -	Verification of deenergized condition. The requirements of this paragraph shall be met before any circuits or equipment can be considered and worked as deenergized.  a) On or about November 24, the employer failed to ensure that circuits and equipment were properly locked out and tagged, failed to release stored electrical energy, and failed to verify the deenergized condition before employees began work on electrical equipment. A maintenance employee was replacing a ballast in an overhead light fixture without a lock and tag applied to the disconnecting means, and without verification that all hazardous energy had been isolated. Stored energy remained in a capacitor, which discharged during the task and caused the employee to fall from an A-frame ladder. As a result, employees were exposed to electrical hazards from contact with energized components.
Recent events (2)
  • — I (S) $8275
  • — Z (S) $16550

1910.333 B02 I

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Dec 10, 2025
Abate by
Jan 29, 2026
Penalty
Initial $16,550 · Current $0 Reduced
29 CFR  1910.333(b)(2)(i):"Procedures." The employer shall maintain a written copy of the procedures outlined in paragraph (b)(2) and shall make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives. Note: The written procedures may be in the form of a copy of paragraph (b) of this section.  a)On or about November 26, 2025, The employer failed to develop and maintain written lockout/tagout (LOTO) procedures for tasks involving electrical maintenance. As a result, an employee was exposed to energized electrical components while working on a ballast, received an electric shock, and fell from a ladder. Employees are exposed to serious hazards, including electrical shock and fall-related injuries.
Recent events (2)
  • — I (S) $0
  • — Z (S) $16550

View University of Dayton's full OSHA safety record →