Fatality or catastrophe inspection · Health discipline

On , OSHA opened a fatality or catastrophe health inspection of A. M. PYROTECHNICS, LLC in 2429 EAST 535TH ROAD, BUFFALO, MO 65622 (NAICS 325998). OSHA activity number 348618356.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch A. M. Pyrotechnics, LLC for free Get an email when a new federal OSHA severe-injury report for A. M. Pyrotechnics, LLC is published. One employer, no account, unsubscribe in one click.
Site address
2429 EAST 535TH ROAD
City
BUFFALO
State
MO
ZIP
65622
Mailing
2429 EAST 535TH ROAD, BUFFALO, MO 65622
Inspection type
Fatality or catastrophe (M)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325998
Employees
3
Ownership type
Private (A)

3 citations on file for this inspection.

1910.109 G02 V

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 10, 2026
Abate by
May 6, 2026
Penalty
Initial $4,256 · Current $0 Reduced
29 CFR 1910.109(g)(2)(v): All electrical switches, controls, motors, and lights located in the mixing room did not conform to the requirements in subpart S of this part for Class II, Division 2 locations.  At a worksite located at or near 2429 East 535th Road, Buffalo, MO 65622:  Employees were exposed to fire and/or explosion hazards. This was demonstrated on or about November 26, 2025, and at times prior to when equipment including but not limited to Central Machinery Cement Mixers were used in the manufacturing of stars and was powered by a plug and cord that was run through an opening in the wall. The employer did not ensure that all electrical switches, controls, motors, and lights located in the mixing room met the requirements in subpart S of this part for Class II, Division 2 locations.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4256

1910.307 C

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 10, 2026
Abate by
May 6, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:  At a worksite located at or near 2429 East 535th Road, Buffalo, MO 65622:  Employees were exposed to fire and/or explosion hazards. This was demonstrated on or about November 26, 2025, and at times prior to when equipment including but not limited to Central Machinery Cement Mixers were used in the manufacturing of stars was powered by a plug and cord that was run through an opening in the wall. The equipment, wiring methods, and installations of equipment was not approved for the hazardous location, or safe for the hazardous location. The employer did not ensure that all electrical switches, controls, motors, and lights located in the mixing room met the requirements in subpart S of this part for Class II, Division 2 locations.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.109 G02 VI C

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 10, 2026
Abate by
May 6, 2026
Penalty
Initial $4,256 · Current $0 Reduced
29 CFR  1910.109(g)(2)(vi)(c): The entire mixing and packaging plant was not cleaned regularly and thoroughly as to prevent excessive accumulation of dust.  At a worksite located at or near 2429 East 535th Road, Buffalo, MO 65622:  Employees were exposed to fire and/or explosion hazards. This was demonstrated on or about November 26, 2025, and at times prior to when comp dust was allowed to accumulate due to inconsistent and poor housekeeping in manufacturing areas of the facility, including but not limited to mixing and packaging areas. Comp dust or composition dust is comprised of black powder and metal salts which are combustible and can catch fire under the right conditions. The employer did not ensure that the entire mixing and packaging areas of the facility/plant were cleaned in a regular and through manner as to prevent the accumulation of dust associated with the manufacturing of fireworks.