Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ABCON AUTOMATION, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ABCON AUTOMATION, INC. in 10991 ST RT 128, HARRISON, OH 45030 (NAICS 238210). OSHA activity number 348659053.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Abcon Automation, INC. — free Get an email when a new federal OSHA severe-injury report for Abcon Automation, INC. is published. One employer, no account, unsubscribe in one click.
Site address
10991 ST RT 128
City
HARRISON
State
OH
ZIP
45030
Mailing
10991 ST RT 128, HARRISON, OH 45030
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
4
Ownership type
A

4 citations on file for this inspection.

1910.22 B

Serious Gravity 5 1 instance 4 exposed
Issued
Feb 4, 2026
Abate by
Mar 24, 2026
Penalty
Initial $3,547 · Current $3,547
29 CFR  1910.22(b):(b) Loads.  The employer must ensure that each walking-working surface can support the maximum intended load for that surface.  a)On or about December 20, 2025, the employer failed to ensure that the interstitial ceiling panels used as a walking-working surface could support the maximum intended load for that surface. Employees were performing work activities such as installing an HVAC motor in the interstitial space above the drop ceiling, while standing on top of a suspended ceiling of Mesa insulated metal panels.  A panel failed and an employee fell approximately 20 to the concrete floor below.
Recent events (2)
  • — I (S) $3547
  • — Z (S) $3547

1910.22 D03

Serious Gravity 5 1 instance 4 exposed
Issued
Feb 4, 2026
Abate by
Mar 24, 2026
Penalty
Initial $3,547 · Current $0 Reduced
29 CFR  1910.22(d)(3):(3) When any correction or repair involves the structural integrity of the walking-working surface, a qualified person performs or supervises the correction or repair.  a)On our about December 20, 2025, the employer did not ensure that a qualified person performed or supervised repair work affecting the structural integrity of an interstitial walking working surface. Employees, performing work activities, including installing an HVAC motor in the interstitial space above the drop ceiling, which required the opening and repairing of the walking working surface were exposed to a fall hazard of approximately 20 feet to the production floor below.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3547

1910.28 B03 I

Serious Gravity 10 1 instance 4 exposed
Issued
Feb 4, 2026
Abate by
Mar 24, 2026
Penalty
Initial $4,965 · Current $4,965
29 CFR  1910.28(b)(3)(i):(3) Holes.  The employer must ensure: (i) Each employee is protected from falling through any hole (including skylights) that is 4 feet (1.2 m) or more above a lower level by one or more of the following:  (A)Covers; (B)Guardrail systems; (C)Travel restraint systems; or (D)Personal fall arrest systems.  a)On or about December 20, 2025, the employer failed to ensure employees were protected from falling through an opening in the ceiling approximately 20 feet above the production floor while performing millwright activities, including hoisting and installing a motor. Employees were standing near and working around a 12-foot section of ceiling panel that had been removed without any cover, guardrail system, or properly anchored fall protection. As a result, employees were exposed to a fall hazard of approximately 20 feet.
Recent events (2)
  • — I (S) $4965
  • — Z (S) $4965

1910.140 C20

Serious Gravity 10 1 instance 4 exposed
Issued
Feb 4, 2026
Abate by
Mar 24, 2026
Penalty
Initial $4,965 · Current $0 Reduced
29 CFR  1910.140(c)(20):(20) Ropes, belts, lanyards, lifelines, and harnesses used for personal fall protection must be protected from being cut, abraded, melted, or otherwise damaged.  a) On or about December 20, 2025, the employer failed to ensure that ropes, belts, lanyards, lifelines, and harnesses used for personal fall protection were protected from being cut, abraded, or otherwise damaged.  Anchor points utilized by employees preforming millwright activities in an interstitial space above a dropped ceiling were wrapped directly around steel structural support beams in the roof  without any protective covers or sleeves to prevent damage. As a result, employees were exposed to fall hazards at approximately 20 feet.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4965

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348659053.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.