Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PARTS AUTHORITY LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PARTS AUTHORITY LLC in 110 OLD COUNTY CIRCLE, WINDSOR LOCKS, CT 06096 (NAICS 423120). OSHA activity number 348667767.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Parts Authority LLC — free Get an email when a new federal OSHA severe-injury report for Parts Authority LLC is published. One employer, no account, unsubscribe in one click.
Establishment
PARTS AUTHORITY LLC
Site address
110 OLD COUNTY CIRCLE
City
WINDSOR LOCKS
State
CT
ZIP
06096
Mailing
110 OLD COUNTY CIRCLE, WINDSOR LOCKS, CT 06096
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423120
Employees
180
Ownership type
A

6 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 22 instances 25 exposed
Issued
Apr 17, 2026
Penalty
Initial $6,384 · Current $4,469 Reduced
29 CFR  1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On, or about, January 5, 2026, electrical equipment was not used in accordance with its listing/labeling:  A.	In the following locations, electrical boxes designed for permanent mounting were used in pendent drop assemblies:  1.	Ground Parcel Receiving Workstation:  Three computer workstations. 2.	Receiving:  Computer workstation adjacent to a red storage rack.  B.	Ship Stations:  Seventeen workstations were energized through a series of extension cords and relocatable power taps.
Recent events (2)
  • — I (S) $4468.8
  • — Z (S) $6384

1910.305 G01 IV A

Serious Gravity 1 17 instances 17 exposed
Issued
Apr 17, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  Ship Stations:  On, or about, January 5, 2026, a series of extension cords were used in lieu of permanent wiring to energize equipment at seventeen workstations.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 A03

Other-than-serious 1 instance 2 exposed
Issued
Apr 17, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.37(a)(3):  Exit route(s) were not kept free and unobstructed:  Dispatch Area for Store:  On, or about, January 5, 2026, a pallet with a tote of items had been placed in the path of the exit door located at the front of the warehouse.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.106 B04 IV G

Other-than-serious 1 instance 2 exposed
Issued
Apr 17, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.106(b)(4)(iv)(g):  The inlet of the fill pipe was not located outside of the building:  Sprinkler Pump Room:  On, or about, January 5, 2026, the fill pipe provided on the 250 gallon tank that contained diesel fuel, a Category 3 flammable liquid, was located inside of the building.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 I A

Other-than-serious 1 instance 2 exposed
Issued
Apr 17, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(i)(A):   For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:  Rear Wall:  On, or about January 5, 2026, a floor mounted bollard was located in the working space for Panel HVC-3, a 480/277 volt General Electric panelboard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 F06 II

Other-than-serious 1 instance 2 exposed
Issued
Apr 17, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.1200(f)(6)(ii):  Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the product identifier and words, pictures, symbols, or combination thereof, which provide at least general information regarding the hazards of the chemicals and which, in conjunction with the other information immediately available to employees under the hazard communication program, would provide employees with the specific information regarding the physical and health hazards of the hazardous chemical:  Sprinkler Pump Room:  On, or about, January 5, 2026, a 250 gallon tank that contained diesel fuel, a Category 3 flammable liquid and central nervous system depressant, was not provided with labeling to identify the contents and the appropriate hazard warning.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Parts Authority LLC's full OSHA safety record →