Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,892Inspections Most recent open 2026-09-03 Last loaded 2026-09-07

OSHA Inspection: BLUE ZOO OKLAHOMA, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BLUE ZOO OKLAHOMA, LLC in 2501 WEST MEMORIAL ROAD, OKLAHOMA CITY, OK 73134 (NAICS 712130). OSHA activity number 348705716.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Blue ZOO Oklahoma, LLC for free Get an email when a new federal OSHA severe-injury report for Blue ZOO Oklahoma, LLC is published. One employer, no account, unsubscribe in one click.
Site address
2501 WEST MEMORIAL ROAD
City
OKLAHOMA CITY
State
OK
ZIP
73134
Mailing
2501 WEST MEMORIAL ROAD SUITE 125A, OKLAHOMA CITY, OK 73134
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Last modified
Data loaded
NAICS code
712130
Employees
18
Ownership type
Private (A)

10 citations on file for this inspection.

1910.23 B09

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 13, 2026
Abate by
Jul 30, 2026
Penalty
Initial $2,128 · Current $1,277 Reduced
29 CFR 1910.23(b)(9): The employer did not ensure that ladders are inspected before initial use in each work shift, and more frequently as necessary, to identify any visible defects that could cause employee injury.   On or about January 22, 2026, located on the first floor behind the aquatic enclosures, employees were required to use a fixed ladder on the reef tank that had visible damage to the rungs and was not being inspected prior to the start of each work shift.
Recent events (1)
  • · Z (S) $2128

1910.23 B10

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 13, 2026
Abate by
Jul 30, 2026
Penalty
Initial $0 · Current $0
29 CFR 1910.23(b)(10): The employer did not ensure that any ladder with structural or other defects as immediately tagged "Dangerous: Do Not Use" or with similar language in accordance with § 1910.145 and removed from service until repaired in accordance with § 1910.22(d), or replaced.  On or about January 22, 2026, located on the first floor behind the aquatic enclosures, employees were required to use a fixed ladder on the reef tank that had visible damage to the rungs and was not tagged or removed from service.
Recent events (1)
  • · Z (S) $0

1910.23 D13 I

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 13, 2026
Abate by
Jul 30, 2026
Penalty
Initial $0 · Current $0
29 CFR 1910.23(d)(13)(i): The employer did not ensure that fixed ladders that do not have cages or wells have a clear width of at least 15 inches (38 cm) on each side of the ladder centerline to the nearest permanent object:  On or about January 22, 2026, located on the first floor behind the aquatic enclosures, employees were required to use a fixed ladder on the reef tank where piping was ran through the rungs and was not clear of at least 15 inches from the centerline.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 5 2 instances 2 exposed
Issued
Jul 13, 2026
Abate by
Jul 30, 2026
Penalty
Initial $4,256 · Current $2,554 Reduced
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or about January 22, 2026, located behind the enclosures on the first and second floor, employees conducted routine husbandry and maintenance activities where labeled electrical equipment was not used and installed in accordance with electrical equipment instructions in the following instances:   Instance a.) Flexible cords being plugged into power strips. Instance b.) Power strips not secured and hanging from building structures.
Recent events (1)
  • · Z (S) $4256

1910.303 G01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 13, 2026
Abate by
Jul 30, 2026
Penalty
Initial $3,547 · Current $2,128 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  On or about January 22, 2026, located on the first floor behind the aquatic enclosures, employees conducted routine husbandry and maintenance activities where the working space for an electrical panel was used for storage.
Recent events (1)
  • · Z (S) $3547

1910.303 G02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 13, 2026
Abate by
Jul 30, 2026
Penalty
Initial $3,547 · Current $2,128 Reduced
29 CFR  1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  On or about January 22, 2026, located behind the enclosures on the second floor, employees conducted routine husbandry and maintenance activities where live electrical parts on a TORK mechanical timer were unguarded and exposed.
Recent events (1)
  • · Z (S) $3547

1910.305 G01 IV B

Serious Gravity 5 4 instances 2 exposed
Issued
Jul 13, 2026
Abate by
Jul 30, 2026
Penalty
Initial $4,256 · Current $2,554 Reduced
29 CFR  1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:  On or about January 22, 2026, located behind the enclosures on the second floor, employees conducted routine husbandry and maintenance activities where flexible cords and cables were run through ceilings and holes in the walls.
Recent events (1)
  • · Z (S) $4256

1910.305 G01 IV D

Serious Gravity 5 5 instances 2 exposed
Issued
Jul 13, 2026
Abate by
Jul 30, 2026
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces:  On or about January 22, 2026, located on the first and second floor behind the aquatic enclosures, employees conducted routine husbandry and maintenance activities where flexible cords were attached to the building surfaces.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV E

Serious Gravity 5 2 instances 2 exposed
Issued
Jul 13, 2026
Abate by
Jul 30, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(E): Flexible cords and cables were used where concealed behind building walls, ceilings, or floors:  On or about January 22, 2026, located behind the enclosures on the second floor, employees conducted routine husbandry and maintenance activities where flexible cords and cables were concealed behind ceiling tiles and walls.
Recent events (1)
  • · Z (S) $0

1910.335 B01

Serious Gravity 1 2 instances 2 exposed
Issued
Jul 13, 2026
Abate by
Jul 30, 2026
Penalty
Initial $2,128 · Current $1,277 Reduced
29 CFR 1910.335(b)(1): Safety signs, safety symbols, or accident prevention tags were not used to warn employees about electrical hazards which may endanger them, as required by 1910.145.  On or about January 22, 2026, located behind the enclosures on the first and second floor, employees conducted routine husbandry and maintenance activities where warning signage was not included on electrical equipment.
Recent events (1)
  • · Z (S) $2128

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 348705716.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.