Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CASINO DEL SOL RESORT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CASINO DEL SOL RESORT in 5655 WEST VALENCIA RD., TUCSON, AZ 85757 (NAICS 721120). OSHA activity number 348709270.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Casino DEL SOL Resort — free Get an email when a new federal OSHA severe-injury report for Casino DEL SOL Resort is published. One employer, no account, unsubscribe in one click.
Site address
5655 WEST VALENCIA RD.
City
TUCSON
State
AZ
ZIP
85757
Mailing
5655 WEST VALENCIA RD., TUCSON, AZ 85757
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721120
Employees
200
Ownership type
A

3 citations on file for this inspection.

1910.253 B04 III

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 27, 2026
Penalty
Initial $7,688 · Current $4,229 Reduced
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:   Chiller Plant:  On or about January 26th  2026, and at times prior to, the employer did not ensure that the oxygen and acetylene compressed gas cylinders were separated by a minimum distance of 20 feet, or by a noncombustible barrier at least 5 ft. high having a fire resistance rating of at least one hour. This condition potentially exposed employee(s) to fire and explosive hazards.
Recent events (2)
  • — I (S) $4229
  • — Z (S) $7688

1910.303 B02

Serious Gravity 5 2 instances 10 exposed
Issued
Feb 27, 2026
Penalty
Initial $6,149 · Current $3,382 Reduced
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  On or about January 26th, 2026, and at times prior thereto, a space heater and a large commercial refrigerator were not plugged in directly to a wall receptacle  which was not used according to the listing and labeling instructions. This condition potentially exposed employee(s) to electrical and/or fire hazard(s).  In the following location(s):  a) Banquet Warehouse - black space heater plugged into an extension cord. b) Street Scape Kitchen - a large commercial refrigerator was plugged into an RPT.
Recent events (2)
  • — I (S) $3382
  • — Z (S) $6149

1910.305 A02 X

Other-than-serious 1 instance 5 exposed
Issued
Feb 27, 2026
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(x):  Flexible cords and cables shall be protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points.  Laundry :  On  or about January 26th, 2026, and at times prior thereto, a flexible cord was laying though the metal bathroom doorway.  This condition potentially exposed employee(s) to shock hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Casino DEL SOL Resort's full OSHA safety record →