OSHA Inspection: HARBISONWALKER INTERNATIONAL, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of HARBISONWALKER INTERNATIONAL, INC. in 111 WEST ST. EUNICE RD., FULTON, MO 65251 (NAICS 327120). OSHA activity number 348782665.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Harbisonwalker International, INC. — free Get an email when a new federal OSHA severe-injury report for Harbisonwalker International, INC. is published. One employer, no account, unsubscribe in one click.
Site address
111 WEST ST. EUNICE RD.
City
FULTON
State
MO
ZIP
65251
Mailing
111 WEST ST. EUNICE RD., FULTON, MO 65251
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327120
Employees
60
Ownership type
A

4 citations on file for this inspection.

1910.146 C07 III

Other-than-serious 1 instance 2 exposed
Issued
Apr 13, 2026
Abate by
Apr 28, 2026
Penalty
Initial $903 · Current $542 Reduced
29 CFR  1910.146(c)(7)(iii): The employer did not document the basis for determining that all hazards in a permit space have been eliminated, through a certification that contains the date, the location of the space, and the signature of the person making the determination. The certification was not made available to each employee entering the space or to that employee's authorized representative.  At 111 West St. Eunice Rd., Fulton, MO, 65251, On March 3, 2026 and at times prior thereto,  the employer did not document the basis for determining that all hazards in a permit space have been eliminated through a certification that contains the date, space location, and the signature of the person making the determination.  Employees enter the Simpson Mixer to perform cleaning and maintenance without substantiating all determinations that all mechanical hazards in the permit space have been eliminated as required by alternate entry provisions.
Recent events (2)
  • — I (O) $541.8
  • — Z (O) $903

1910.147 C05 II B

Other-than-serious 1 instance 2 exposed
Issued
Apr 13, 2026
Abate by
Apr 28, 2026
Penalty
Initial $903 · Current $542 Reduced
29 CFR  1910.147(c)(5)(ii)(B): Lockout and tagout devices were not standardized within the facility in at least one of the following criteria: color; shape; or size:  On or about March 3, 2026 at 111 West St. Eunice Road, Fulton, Missouri, 65251, employees utilized security locks as lockout devices that were not standardized thereby exposing them to hazards associated with the unexpected energization of equipment.
Recent events (2)
  • — I (O) $541.8
  • — Z (O) $903

1910.147 C06 I

Other-than-serious 1 instance 2 exposed
Issued
Apr 13, 2026
Abate by
May 13, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:  At 111 West St. Eunice Rd., Fulton, MO, 65251, on March 3, 2026 and at times prior thereto, employees were exposed to hazards associated with unexpected energization of equipment.  Procedures were not inspected annually to ensure that the procedure and the requirement sof the standard were met.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 B01 VIII

Other-than-serious 1 instance 2 exposed
Issued
Apr 13, 2026
Abate by
May 13, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(1)(viii): Electric equipment was not free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment was not determined using the following considerations: Other factors that contribute to the practical safeguarding of persons using or likely to come in contact with the equipment.  At 111 West St. Eunice Rd., Fulton, MO, 65251, on March 3, 2026 and at times prior thereto, employees were exposed to electrical hazards associated with a 480 volt panel and a shower wash station.   Employees were exposed to a shower wash station which was located above a 480 volt panel.  If activated the water from the shower would make contact with the panel causing an electrical hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348782665.