Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,124Inspections Most recent open 2026-08-25 Last loaded 2026-08-28

OSHA Inspection: ADCO COMPANIES, LTD.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ADCO COMPANIES, LTD. in 1725 PINE ST., MONTGOMERY, AL 36106 (NAICS 811310). OSHA activity number 348861303.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Adco Companies, LTD. for free Get an email when a new federal OSHA severe-injury report for Adco Companies, LTD. is published. One employer, no account, unsubscribe in one click.
Site address
1725 PINE ST.
City
MONTGOMERY
State
AL
ZIP
36106
Mailing
3657 PINE LANE, BESSEMER, AL 35022
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Last modified
Data loaded
NAICS code
811310
Employees
70
Ownership type
Private (A)

6 citations on file for this inspection.

1910.333 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 10, 2026
Abate by
Aug 7, 2026
Penalty
Initial $6,753 · Current $5,402 Reduced
29 CFR  1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:  a) On or about April 02, 2026, in the Goode Building Main Mechanical Room at Jackson Hospital in Montgomery, Alabama, employees worked to replace fuses within an electrical cabinet without first securing the power.
Recent events (2)
  • · I (S) $5402.4
  • · Z (S) $6753

1910.333 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 10, 2026
Abate by
Jul 20, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.333(a)(2): Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved:  a) On or about April 02, 2026, in the Goode Building Main Mechanical Room at Jackson Hospital in Montgomery, Alabama, where exposed, live parts were not deenergized, the employer did not ensure that alternative safety-related work practices were used to protect employees involved while pulling blown fuses from the live electrical panel.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.335 A02 I A

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 10, 2026
Abate by
Aug 7, 2026
Penalty
Initial $6,753 · Current $5,402 Reduced
29 CFR  1910.335(a)(2)(i)(A): Fuse handling equipment, insulated for the circuit voltage was not used to remove or install fuses when fuse terminals were energized.  a) On or about April 02, 2026, in the Goode Building Main Mechanical Room at Jackson Hospital in Montgomery, Alabama, employees did not use insulated fuse handling equipment to remove fuses from an electrical panel on the electrical boiler.
Recent events (2)
  • · I (S) $5402.4
  • · Z (S) $6753

1910.335 A01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 10, 2026
Abate by
Aug 7, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  a) On or about April 02, 2026, in the Goode Building Main Mechanical Room at Jackson Hospital in Montgomery, Alabama, employees worked without electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected such as but not limited to the face, arms and hands and for the work being performed on an electrical panel on the electrical boiler.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1904.41 A01 I

Other-than-serious 1 instance 1 exposed
Issued
Jul 10, 2026
Penalty
Initial $1,125 · Current $900 Reduced
29 CFR  1904.41(a)(1)(i): The employer's establishment had 20-249 employees during the previous calendar year and is classified in an industry listed in Appendix A to Subpart E of Part 1904, but the employer failed to electronically submit information from the establishment's OSHA Form 300A by March 2nd.  (a) ADCO Companies, LTD, Bessemer, AL ;  On or about March 2, 2026, the employer failed to electronically submit information from their OSHA Form 300A, Summary of Work-Related Injuries and Illnesses or equivalent form, for calendar year 2025 on or before March 2, 2026.  The establishment employed 70 employees during calendar year 2025 and was classified under NAICS code 238220.
Recent events (2)
  • · I (O) $900
  • · Z (O) $1125

1910.132 D01

Other-than-serious 1 instance 1 exposed
Issued
Jul 10, 2026
Abate by
Jul 20, 2026
Penalty
Initial $0 · Current $0
29 CFR  1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE):  a) On or about April 02, 2026 and at times prior thereto, in the Goode Building Main Mechanical Room at Jackson Hospital in Montgomery, Alabama, the employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment for employees performing maintenance tasks on an electric boiler.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 348861303.