Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31

OSHA Accident Investigation · Summary #221724602

PROLEC-GE WAUKESHA, INC.

Event
Burn, Electric Arc, Electric Arc Flash, Electric Shock, Electrical, Electrocuted, Power Line Worker
NAICS
423850
Inspection type
Federal Agency
Activity number
#347921660
Employer profile
PROLEC-GE WAUKESHA, INC.
Summary number
221724602
Report ID
0523400

Event description

Employee dies from electrocution after arc flash

Investigation abstract

At 2:30 p.m. on December 7, 2024, Employee #1, a test technician at Prolec-GE the surface of the transformer top, sustaining burn and electrical shock injuries resulting in electrocution. The electrical power involved was approximately 8,000 volts. Waukesha, Inc., was working alone in the transformer manufacturing test area. Using a scissor lift, the employee elevated approximately 15 feet to the top of a newly built high-voltage electrical transformer to disconnect three-phase power by removing power leads as part of teardown after an electrical test. The electrical circuit had not been effectively deenergized or verified as deenergized visually or with testing equipment prior to the work. While loosening a nut securing one of the power leads, an arc flash occurred, causing electrical current to pass through the employee. The employee was thrown onto

Victim

  1. #1 Fatality Age 34 M

    Event type
    13
    Occupation code
    797