Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,288Inspections Most recent open 2026-07-24 Last loaded 2026-07-29

OSHA Inspection: CROWN CENTRAL PETROLEUM CORP

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of CROWN CENTRAL PETROLEUM CORP in 111 RED BLUFF, PASADENA, TX 77506 (NAICS 000000). OSHA activity number 100267467.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Crown Central Petroleum Corp — free Get an email when a new federal OSHA severe-injury report for Crown Central Petroleum Corp is published. One employer, no account, unsubscribe in one click.
Site address
111 RED BLUFF
City
PASADENA
State
TX
ZIP
77506
Mailing
PO BOX 1759, HOUSTON, TX 77001
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
2911
Employees
386
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Serious 1 instance 2 exposed
Issued
Feb 13, 1986
Abate by
Mar 19, 1986
Penalty
Initial $490 · Current $490
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees in that:
a) On or about October 24, 1985, employees were exposed to the hazard
of being struck by fragments of a ruptured neutralizer drum or
serious burns from teh ensuing fire due to the over pressurization
of such drum (Alky Unit #2).
One feasible and acceptable method, among others, to correct this hazard
is to provide the neutralizer drum or closed relief system with a
pressure sensing device with transmitting means to the control room and
capability to activate an alarm to alert operatorsof pressure build-up.

View Crown Central Petroleum Corp's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 100267467.