PITTSBURGH, PA —
OSHA Inspection: SHENANGO
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of SHENANGO in 200 NEVILLE ROAD, PITTSBURGH, PA 15225 (NAICS 000000). OSHA activity number 107154452.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SHENANGO
- Site address
- 200 NEVILLE ROAD
- City
- PITTSBURGH
- State
- PA
- ZIP
- 15225
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 3312
- Employees
- 300
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.120 Q06 IIIA
- Issued
- Mar 16, 1992
- Abate by
- Apr 15, 1992
- Penalty
- Initial $975 · Current $975
1910.120 Q06 IIID
- Issued
- Mar 16, 1992
- Abate by
- Apr 15, 1992
1910.134 E03
- Issued
- Mar 16, 1992
- Abate by
- Apr 15, 1992
5(a)(1)
- Issued
- Dec 5, 1991
- Abate by
- Mar 6, 1992
- Penalty
- Initial $975 · Current $500 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The %% employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that Boiler House employees were not adequately protected against hazardous concentrations of carbon monoxide from leaking coke oven gas while working throughout the boiler house building: a) Boiler House: The #10 water tender and #10 water tender helper were potentially exposed to high levels of carbon monoxide and were not provided with an adequate alarm and warning system. Employees are potentially exposed to carbon monoxide while working throughout the boiler house building (approximately 220 ft. x 50 ft.). The fuel used in the boiler house is coke oven gas which contains 4% carbon monoxide. Feasible and useful abatement methods for reducing this hazard, among others, are: 1. The installation of permanently installed carbon monoxide alarms at various locations on both floors of the boiler house building. 2. Personal carbon monoxide meters with audible alarms to be carried by workers when responding to and repairing coke oven gas leaks.
Recent events (2)
- — F (S) $500.00
- — Z (S) $975.00
1910.120 Q01
- Issued
- Dec 5, 1991
- Abate by
- Apr 15, 1992
- Penalty
- Initial $975 · Current $500 Reduced
Recent events (2)
- — F (S) $500.00
- — Z (S) $975.00
1910.120 Q06 IIID
- Issued
- Dec 5, 1991
- Abate by
- Mar 6, 1992
- Penalty
- Initial $975 · Current $975
Recent events (2)
- — F (S) $975.00
- — Z (S) $975.00
1910.134 E03
- Issued
- Dec 5, 1991
- Abate by
- Mar 6, 1992
Recent events (2)
- — F (S)
- — Z (S)
More inspections at Shenango
View Shenango's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 107154452.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.