OSHA Inspection: FLORIDA POWER & LIGHT COMPANY

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of FLORIDA POWER & LIGHT COMPANY in 510 BAY ISLES ROAD, LONGBOAT KEY, FL 33548 (NAICS 000000). OSHA activity number 109607424.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Florida Power & Light Company — free Get an email when a new federal OSHA severe-injury report for Florida Power & Light Company is published. One employer, no account, unsubscribe in one click.
Site address
510 BAY ISLES ROAD
City
LONGBOAT KEY
State
FL
ZIP
33548
Mailing
1177 NORTH LIME AVE., SARASOTA, FL 34237
Inspection type
Accident-driven (A)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
000000
SIC code (legacy)
4911
Employees
3
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 3 exposed
Issued
Sep 8, 1994
Abate by
Oct 11, 1994
Penalty
Initial $5,000 · Current $2,000 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  the
employer did not
furnish employment and a place of employment which were free from
recognized hazards
that were causing or likely to cause death or serious physical harm to
employees in that
employees were exposed to the hazard of electrical shock and burns:
a)  At the inspection site, employees were exposed to an electrical hazard
by using an
"underground elbow" phasing meter (FPL#561-A-239)and purposely attempting
to
contact bare energized parts(23KV phase to phase & 13.2KV phase to ground)
with a
probe of the meter that was not designed to be used on bare energized
parts, on or
about 04/02/94.
b)  At the inspection site, employees were exposed to an electrical hazard
by being
too close to bare energized parts or conductive objects(phasing meter
FPL#561-A-
239)that were in contact or near contact to bare energized parts(23KV
phase
to phase
& 13.2KV phase to ground)in violation of acceptable approach distances
without
using any type of acceptable insulation, on or about 04/02/94.
One feasible and acceptable abatement method, among others, to correct
this hazard is
to train employees on safe operation of phasing meters and verify employee
comprehension of training on all phasing equipment available for use by the
employees on an ongoing basis at intervals necessary to maintain
familiarity with all
equipment that is available for use. Eliminating similar types of phasing
equipment
with different functions and multiple models of equipment for the same
functions
would reduce the possibility of confusion.  Employees must wear rubber
gloves rated
for the voltages exposed to when safe approach distances are violated or
use some
other equivalent means to provide insulation from the energized parts.