LONGBOAT KEY, FL —
OSHA Inspection: FLORIDA POWER & LIGHT COMPANY
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of FLORIDA POWER & LIGHT COMPANY in 510 BAY ISLES ROAD, LONGBOAT KEY, FL 33548 (NAICS 000000). OSHA activity number 109607424.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FLORIDA POWER & LIGHT COMPANY
- Site address
- 510 BAY ISLES ROAD
- City
- LONGBOAT KEY
- State
- FL
- ZIP
- 33548
- Mailing
- 1177 NORTH LIME AVE., SARASOTA, FL 34237
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 3
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Sep 8, 1994
- Abate by
- Oct 11, 1994
- Penalty
- Initial $5,000 · Current $2,000 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: the employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of electrical shock and burns: a) At the inspection site, employees were exposed to an electrical hazard by using an "underground elbow" phasing meter (FPL#561-A-239)and purposely attempting to contact bare energized parts(23KV phase to phase & 13.2KV phase to ground) with a probe of the meter that was not designed to be used on bare energized parts, on or about 04/02/94. b) At the inspection site, employees were exposed to an electrical hazard by being too close to bare energized parts or conductive objects(phasing meter FPL#561-A- 239)that were in contact or near contact to bare energized parts(23KV phase to phase & 13.2KV phase to ground)in violation of acceptable approach distances without using any type of acceptable insulation, on or about 04/02/94. One feasible and acceptable abatement method, among others, to correct this hazard is to train employees on safe operation of phasing meters and verify employee comprehension of training on all phasing equipment available for use by the employees on an ongoing basis at intervals necessary to maintain familiarity with all equipment that is available for use. Eliminating similar types of phasing equipment with different functions and multiple models of equipment for the same functions would reduce the possibility of confusion. Employees must wear rubber gloves rated for the voltages exposed to when safe approach distances are violated or use some other equivalent means to provide insulation from the energized parts.
Recent events (2)
- — F (S) $2000.00
- — Z (S) $5000.00
More inspections at Florida Power & Light Company