Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ALLIED SIGNAL CORP.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ALLIED SIGNAL CORP. in 3330 S. THIRD STREET, IRONTON, OH 45638 (NAICS 000000). OSHA activity number 121984165.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Allied Signal Corp. — free Get an email when a new federal OSHA severe-injury report for Allied Signal Corp. is published. One employer, no account, unsubscribe in one click.
Establishment
ALLIED SIGNAL CORP.
Site address
3330 S. THIRD STREET
City
IRONTON
State
OH
ZIP
45638
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
2865
Employees
40
Ownership type
A
Industry flags
Manufacturing safety.

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 20 exposed
Issued
May 20, 1999
Abate by
May 25, 1999
Penalty
Initial $7,000 · Current $5,000 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not
furnish employment and a place of employment which were free from
recognized hazards
that were causing or likely to cause death or serious physical harm to
employees in that
employees were exposed to:
(a)Fire and explosion from the release of combustible liquid vapors from
tank #8,
in that the tank and all tank appurtenances, including, but not limited to,
emergency vents (including venting to a safe location) sample valves and
dip
holes were not properly inspected and maintained to ensure that they
function
as intended, such as, but not limited to the following:
1)The sample valve (run off) was corroded and failed at its thread section.
2)The emergency vent hatch was prevented from opening as designed because
of
a catwalk extension installed over the hatch.  In addition, the openings
on top
of the tank was not designed to vent to a safe location.
3)The dip hole cover at the top of the tank was not of the self-closing
type, nor
was it of the liquid tight design.
Among other methods, feasible and acceptable abatement methods to abate
these hazards
would include development and implementation of a program to inspect, test
and maintain the
quality and integrity of all critical equipment associated with processing
tanks including safe
venting locations in accordance with recognized industry practices, such
as the American
Petroleum Institute (API 750), NFPA 30 Code for Flammable and Combustible
liquids and
OSHA's Process Safety Management Standard 29 CFR 1910.119.