DECATUR, IL —
OSHA Inspection: ALL TRI-R, INC.
Accident-driven inspection · Health discipline
At a glance
On , OSHA opened an accident-driven health inspection of ALL TRI-R, INC. in 4666 FARIES PARKWAY, DECATUR, IL 62525 (NAICS 000000). OSHA activity number 122195969.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ALL TRI-R, INC.
- Site address
- 4666 FARIES PARKWAY
- City
- DECATUR
- State
- IL
- ZIP
- 62525
- Mailing
- 2320 E LOGAN ST., DECATUR, IL 62526
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- Yes
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 1711
- Employees
- 120
- Ownership type
- A
Citations
3 citations on file for this inspection.
5(a)(1)
- Issued
- Jun 6, 1996
- Abate by
- Jun 11, 1996
- Penalty
- Initial $2,500 · Current $1,750 Reduced
General-duty citation text
Section 5(a)(1) The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to potential atmospheric and thermal hazards when entering a horizontal waste heat duct located in the boiler room of the corn processing plant at Archer Daniels Midland. The employees entered the duct, which is a permit required confined space as defined in 29 CFR 1910.146, on 1/5/96 and 1/6/96, and used electric reciprocating saws and gas powered chop saws to cut and demolish the duct. Atmospheric testing for carbon monoxide was not performed, either before or during the entry. Testing for oxygen deficiency or combustible gas was not performed during the entry. An entry permit was not issued. Branch ducts connected the waste heat duct to exhaust stacks for the gas fired boilers, and these branch ducts were not blanked to isolate the horizontal waste heat duct from the exhaust stacks. Among other methods, a feasible and acceptable abatement could include: 1.Perform the entry in accordance with OSHA's permit required confined space standard, 29 CFR 1910.146. 2.Implement measures that would change the horizontal duct from a permit required confined space to a confined space. Such measures would include, but not necessarily be limited to, prohibiting the use of gas powered saws inside the duct, and disconnecting the duct from the exhaust stacks prior to entry. Disclaimers: a.The employer is not limited to the abatement methods suggested by OSHA; b.The methods explained are general and may not be effective in all cases; c.The employer is responsible for selecting and carrying out an effective abatement method.nt
Recent events (2)
- — I (S) $1750.00
- — Z (S) $2500.00
1926.55 A
- Issued
- Jun 6, 1996
- Abate by
- Jun 11, 1996
- Penalty
- Initial $3,500 · Current $2,450 Reduced
0560
Recent events (2)
- — I (S) $2450.00
- — Z (S) $3500.00
1926.55 B
- Issued
- Jun 6, 1996
- Abate by
- Jun 11, 1996
0560
Recent events (2)
- — I (S)
- — Z (S)
More inspections at ALL Tri-R, INC.
View ALL Tri-R, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 122195969.