Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GRACE INDUSTRIES INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of GRACE INDUSTRIES INC. in 329 BEND HILL RD., FREDONIA, PA 16124 (NAICS 000000). OSHA activity number 300283512.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Grace Industries INC. — free Get an email when a new federal OSHA severe-injury report for Grace Industries INC. is published. One employer, no account, unsubscribe in one click.
Site address
329 BEND HILL RD.
City
FREDONIA
State
PA
ZIP
16124
Mailing
P.O. BOX 167, TRANSFER, PA 16154
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
000000
SIC code (legacy)
3648
Employees
30
Ownership type
A

7 citations on file for this inspection.

5(a)(1)

Serious Gravity 02 1 instance 20 exposed
Issued
May 30, 2000
Abate by
Jun 2, 2000
Penalty
Initial $700 · Current $250 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to:
a.) Production Area - Employee(s) were potentially exposed to flying
plastic
shards, plastic
projectiles (pipe fragments), and decompressing air at 100 psi because
polyvinyl chloride (PVC)
plastic pipes and plastic pipe fittings were being used to transport
compressed air. The Plastic
Pipe Institute's Recommendation B of 1972 and revised Recommendation B of
1997 requires
PVC piping used for the transport of compressed air to be buried or
encased in shatter resistant
materials. Furthermore, the manufacturers of PVC plastic pipes and plastic
pipe fittings warn
against the use of PVC pipes/fittings for the transportation of compressed
air. The PVC
pipe/fitting manufacturers convey these warnings verbally through sales
personnel/distributors,
web sites, catalogs, product literature, and on cans of solvent cement.
ASME/ANSI B31.8 -
1968/1986 Transmission and Distribution Piping Systems Standard prohibits
the installation of
plastic pipe airline systems above ground except where the above ground
portion of the plastic
service line is completely enclosed in a conduit or casing of sufficient
strength to provide
protection from external damage and deterioration.
FEASIBLE METHODS TO CORRECT THE HAZARD:
OPTION #1: Encase the PVC pipes and PVC pipe fittings in shatter resistant
materials e.g.
metal pipes, wooden box conduit lined with fiberglass, steel box conduit
etc.
OPTION #2: Remove the PVC pipes and PVC pipe fittings.  Install metal
pipes and metal pipe
fittings that meet ASTM specifications for transporting compressed air.
OPTION #3: Remove the PVC pipes and PVC pipe fittings.  Install plastic
pipes and plastic
pipe fittings that meet ASTM specifications for transporting compressed
air.  Three companies
currently manufacture compressed air plastic pipe systems.  These systems
utilize specialized
acrylonitrile-butadiene-styrene (ABS) plastic or high density poly
ethylene (HDPE) plastic.
Manufacturers and suppliers of this type of piping can be found on the
Internet.
Note: DO NOT confuse the ABS utilized in the specialized compressed air
systems with
ABS-DVW.  ABS-DVW is available at most hardware stores and home centers.
ABS-DVW is
not designed to transport compressed air.ressed
Recent events (2)
  • — I (S) $250.00
  • — Z (S) $700.00

1910.303 G02 I

Serious Gravity 01 1 instance 5 exposed
Issued
May 30, 2000
Abate by
Jun 2, 2000
Penalty
Initial $446 · Current $250 Reduced
Recent events (2)
  • — I (S) $250.00
  • — Z (S) $446.00

1910.1200 E01

Serious Gravity 01 1 instance 20 exposed
Issued
May 30, 2000
Abate by
Jul 5, 2000
Penalty
Initial $525 · Current $300 Reduced
Recent events (2)
  • — I (S) $300.00
  • — Z (S) $525.00

1910.1200 F05 I

Serious Gravity 01 1 instance 20 exposed
Issued
May 30, 2000
Abate by
Jul 5, 2000

1910.1200 F05 II

Serious Gravity 01 1 instance 20 exposed
Issued
May 30, 2000
Abate by
Jul 5, 2000

1910.1200 H

Serious Gravity 01 1 instance 20 exposed
Issued
May 30, 2000
Abate by
Jul 5, 2000

1910.1025 D02

Other-than-serious Gravity 03 1 instance 10 exposed
Issued
May 30, 2000
Abate by
Jul 5, 2000
Penalty
Initial $350 · Current $150 Reduced
Recent events (2)
  • — I (O) $150.00
  • — Z (O) $350.00

View Grace Industries INC.'s full OSHA safety record →