OSHA Inspection: WELLIVER MCGUIRE, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of WELLIVER MCGUIRE, INC. in 300 CAMPUS DRIVE UNIV PITTSBURGH BRADFORD, BRADFORD, PA 16701 (NAICS 000000). OSHA activity number 303708523.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Welliver Mcguire, INC. for free Get an email when a new federal OSHA severe-injury report for Welliver Mcguire, INC. is published. One employer, no account, unsubscribe in one click.
Site address
300 CAMPUS DRIVE UNIV PITTSBURGH BRADFORD
City
BRADFORD
State
PA
ZIP
16701
Mailing
911 STOWELL STREET P.O. BOX 90, ELMIRA, NY 14901
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (Y)
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
1542
Employees
70
Ownership type
Private (A)
Industry flags
Construction safety.

5 citations on file for this inspection.

5(a)(1)

Other-than-serious Gravity 02 1 instance 4 exposed
Issued
Jun 11, 2002
Abate by
Jul 8, 2002
Penalty
Initial $500 · Current $325 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not furnish employment
and a place of employment which were free from recognized hazards that
were causing or likely to cause
death or serious physical harm to employees in that employees were
potentially exposed to fire and explosion
hazards from the ignition of natural gas leaks because the hose, hose
connections, & manual shut-off valve
associated with portable space heating devices were not installed
correctly:
a.) University of Pittsburgh ~ Bradford Campus/Bradford, PA/Sports Complex
- From the T-
connection in the corner of the gymnasium, a mainliner hose (red color)
was routed vertically then
horizontally along the gymnasium's wall.  The mainliner hose was then
routed through a hole in the
wall into the corridor off of the buildings main lobby. The hose proceeded
down the wall and was
routed across the floor to a portable space heater (Silent glow/150,000
BTU).  The mainliner hose,
hose connections, and manual shut-off valve were not installed in
accordance with the National Fuel
Gas Code and ANSI A10.10 - 1990 in that:
(1) The mainliner hose & its connectors were not listed/labeled for use
with natural gas.
(2) Slip-end connectors and ring keepers (circular clamp with screw
tightener) were utilized to
affix the hose to the T-connection and the portable space heater
(3) The mainliner hose was routed through a hole in the wall to the
corridor area
(4) The total run of the mainliner hose exceeded 25-feet
(5) The manual gas shut-off valve was not located within 6-feet of the
Silent Glow space heater
ABATEMENT NOTE:
Among other methods, feasible and acceptable abatement methods to correct
the hazard are to comply
with applicable requirements noted in ANSI A10.10-1990 ~ Safety
Requirements for Space Heating
Devices - Section 7 &  NFPA 54/ANSI Z223.1-1999 ~ National Fuel Gas Code
Section 5.5
Hose & Hose Connections:
National Fuel Gas Code (NFPA 54/ANSI Z223.1) Sections 5.5.1 & 5.5.2
requires gas utilization
equipment to be connected to the buildings piping with listed hosed and
hose connectors. ANSI
A10.10 Section 7.3.11 requires hoses and fittings to be the correct type
for the fuel that is utilized by
the heating unit.
National Fuel Gas Code (NFPA 54/ANSI Z223.1) Sections 5.5.2 & 5.5.3
requires gas hose to be the
minium practical length and not pass through walls, partitions, ceilings,
or floors.  ANSI A10.10
Section 7.3.9 & 7.3.16 requires the hose and fittings to be protected
against damage and located to
minimize damage. ANSI A10.10 Section 7.3.10. requires the total run of the
hose to be short as
practicable and not exceed 25-feet.
ANSI A10.10 Section 7.3.15 prohibits the use of slip-end connectors and
ring keepers. ANSI A10.10
Section 7.3.14 requires the hose to be securely connected to fittings via
a
mechanical method.
Manual Shut-off Valve:
National Fuel Gas Code  (NFPA 54/ANSI Z223.1) Section 5.5.4 requires the
manual shut-off valve to
be plainly marked and located within 6-feet of the equipment served.nt
Recent events (2)
  • · I (O) $325.00
  • · Z (S) $500.00

1926.502 B01

Other-than-serious Gravity 01 1 instance 3 exposed
Issued
Jun 11, 2002
Abate by
Jun 14, 2002

1926.502 B02

Other-than-serious Gravity 01 1 instance 4 exposed
Issued
Jun 11, 2002
Abate by
Jun 14, 2002

1926.502 B03

Other-than-serious Gravity 01 1 instance 4 exposed
Issued
Jun 11, 2002
Abate by
Jun 14, 2002

1926.502 I03

Other-than-serious Gravity 01 1 instance 4 exposed
Issued
Jun 11, 2002
Abate by
Jun 14, 2002

View Welliver Mcguire, INC.'s full OSHA safety record →