LACYGNE, KS —
OSHA Inspection: KANSAS CITY POWER & LIGHT LACYGNE GENERATOR
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of KANSAS CITY POWER & LIGHT LACYGNE GENERATOR in 25166 E. 2200 RD., LACYGNE, KS 66040 (NAICS 000000). OSHA activity number 305032260.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KANSAS CITY POWER & LIGHT LACYGNE GENERATOR
- Site address
- 25166 E. 2200 RD.
- City
- LACYGNE
- State
- KS
- ZIP
- 66040
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 258
- Ownership type
- A
Citations
1 citation on file for this inspection.
1910.269 V01 II
- Issued
- Mar 3, 2003
- Abate by
- Mar 6, 2003
- Penalty
- Initial $4,500 · Current $4,500
General-duty citation text
Section 5(a)1 of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire, burns, and inhalation hazards: On or about December 20, 2002, employee preforming a routine check of the hot and cold air dampers, located on the mezzanine level in unit 2, was exposed to fire and explosion hazards when an excess amount of heated air ruptured the blow out plate. The heated air, approximatley 600 degrees fahrenheit, was vented inside the building. Employees were exposed to hazards associated with fire, burns, and inhalation. AMONG OTHER METHODS, ONE FEASIBLE AND ACCEPTABLE METHOD TO CORRECT THIS HAZARD IS: Install hot air duct that will not 'blow out' when exposed to unusual or extreme pressures, or provide exterior venting for the hot air as referenced in ANSI B31.1 - 1977 American National Standard Power Piping. 29 CFR 1903.19(c)(2) abatement of the above violation was verified at the time of inspection, no certification is required.tion
Recent events (2)
- — F (S) $4500.00
- — Z (S) $4500.00
More inspections at Kansas City Power & Light Lacygne Generator
View Kansas City Power & Light Lacygne Generator's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in KS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 305032260.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.