Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WISCONSIN PUBLIC SERVICE

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of WISCONSIN PUBLIC SERVICE in WEYERHAEUSER CO., ROTHSCHILD, WI 54474 (NAICS 237130). OSHA activity number 306798679.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Wisconsin Public Service — free Get an email when a new federal OSHA severe-injury report for Wisconsin Public Service is published. One employer, no account, unsubscribe in one click.
Site address
WEYERHAEUSER CO.
City
ROTHSCHILD
State
WI
ZIP
54474
Mailing
7019 W. STEWART AVE., WAUSAU, WI 54401
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
SIC code (legacy)
1623
Employees
400
Ownership type
A

2 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 2 instances 2 exposed
Issued
May 9, 2005
Abate by
May 13, 2005
Penalty
Initial $4,500 · Current $2,565 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to electrical arc flash:
a) At the Weston WPS Power Plant #4, an arc flash hazard analysis was not
conducted.
Employees, were working within the flash boundary (that was not determined
prior to exposure)
while testing on an energized 6.9KV primary/480V secondary panel board
without the
appropriate personal protective clothing or equipment and were exposed to
the hazard of
electrical burns due to arc flash.
Among feasible means of abatement would be to comply with the 2004 Edition
of the
National Fire Protection Association (NFPA) 70E, Standard for Electrical
Safety in the
Workplace, Article 130, Section 130.3 Flash Hazard analysis: to determine
the
flash protection
boundary, Article 110, Section 110.7(G) Job Briefing: covers hazards
associated with the job,
work procedures involved.
Abatement Certification or Abatement Documentation required.tion
Recent events (2)
  • — I (S) $2565.00
  • — Z (S) $4500.00

1926.95 A

Serious Gravity 05 1 instance 2 exposed
Issued
May 9, 2005
Abate by
May 12, 2005
Penalty
Initial $3,150 · Current $1,770 Reduced
Recent events (2)
  • — I (S) $1770.00
  • — Z (S) $3150.00

View Wisconsin Public Service's full OSHA safety record →