ROTHSCHILD, WI —
OSHA Inspection: WISCONSIN PUBLIC SERVICE
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of WISCONSIN PUBLIC SERVICE in WEYERHAEUSER CO., ROTHSCHILD, WI 54474 (NAICS 237130). OSHA activity number 306798679.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WISCONSIN PUBLIC SERVICE
- Site address
- WEYERHAEUSER CO.
- City
- ROTHSCHILD
- State
- WI
- ZIP
- 54474
- Mailing
- 7019 W. STEWART AVE., WAUSAU, WI 54401
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237130
- SIC code (legacy)
- 1623
- Employees
- 400
- Ownership type
- A
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- May 9, 2005
- Abate by
- May 13, 2005
- Penalty
- Initial $4,500 · Current $2,565 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to electrical arc flash: a) At the Weston WPS Power Plant #4, an arc flash hazard analysis was not conducted. Employees, were working within the flash boundary (that was not determined prior to exposure) while testing on an energized 6.9KV primary/480V secondary panel board without the appropriate personal protective clothing or equipment and were exposed to the hazard of electrical burns due to arc flash. Among feasible means of abatement would be to comply with the 2004 Edition of the National Fire Protection Association (NFPA) 70E, Standard for Electrical Safety in the Workplace, Article 130, Section 130.3 Flash Hazard analysis: to determine the flash protection boundary, Article 110, Section 110.7(G) Job Briefing: covers hazards associated with the job, work procedures involved. Abatement Certification or Abatement Documentation required.tion
Recent events (2)
- — I (S) $2565.00
- — Z (S) $4500.00
1926.95 A
- Issued
- May 9, 2005
- Abate by
- May 12, 2005
- Penalty
- Initial $3,150 · Current $1,770 Reduced
Recent events (2)
- — I (S) $1770.00
- — Z (S) $3150.00
More inspections at Wisconsin Public Service
View Wisconsin Public Service's full OSHA safety record →
More inspections in this industry (NAICS 237130)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 306798679.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.