Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: STERLING PIPE & TUBE INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of STERLING PIPE & TUBE INC. in 5335 ENTERPRISE RD., TOLEDO, OH 43612 (NAICS 331210). OSHA activity number 309443471.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sterling Pipe & Tube INC. — free Get an email when a new federal OSHA severe-injury report for Sterling Pipe & Tube INC. is published. One employer, no account, unsubscribe in one click.
Site address
5335 ENTERPRISE RD.
City
TOLEDO
State
OH
ZIP
43612
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331210
SIC code (legacy)
3317
Employees
52
Ownership type
A
Industry flags
Manufacturing safety.

7 citations on file for this inspection.

5(a)(1)

Serious Gravity 03 2 instances 2 exposed
Issued
Dec 21, 2006
Abate by
Jan 11, 2007
Penalty
Initial $1,375 · Current $750 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees, in that the company
did not perform periodic inspections on the 2X line crane and the 2K line
crane:
a.Sterling Pipe & Tube, Inc. located in Toledo, Ohio:  On or about
September 6, 2006,
the employer did not ensure the company performed periodic inspections on
the 2X line
5 ton crane.  The crane was missing an alarm, hook safety latch, pendant
control
was
missing function labels for the control buttons, the pendant control box
was missing a
large section of the housing, and the hoist rope was double reaving on the
hoisting drum.
b.Sterling Pipe & Tube, Inc. located in Toledo, Ohio:  On or about
September 6, 2006,
the employer did not ensure the company performed periodic inspections on
the 2K line
7.5 ton crane.  The crane was equipped with a malfunctioning safety latch
on the hook
and the pendant control was missing function labels for the control
buttons.
Among other methods, one feasible and acceptable method to correct this
hazard is to
ensure the cranes are inspected at least annually according to ANSI
B30.17-2003
"Overhead and Gantry Cranes (Top Running Bridge, Single Girder, Underhung
Hoist)".
In accordance with 29 CFR 1903.19(c), abatement certification is required
for
this
violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
  • — I (S) $750.00
  • — Z (S) $1375.00

1910.179 J03

Serious Gravity 03 1 instance 2 exposed
Issued
Dec 21, 2006
Abate by
Jan 11, 2007
Recent events (2)
  • — I (S)
  • — Z (S)

5(a)(1)

Serious Gravity 03 2 instances 2 exposed
Issued
Dec 21, 2006
Abate by
Jan 4, 2007
Penalty
Initial $1,375 · Current $750 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees, in that the crane
hooks for the 2X line crane and the 2K line crane were either missing a
safety latch or the safety
latch was malfunctioning:
a.Sterling Pipe & Tube, Inc. located in Toledo, Ohio:  On or about
September 6, 2006,
the employer did not ensure the 2X line 5 ton crane hook was equipped with
a
functioning safety latch.
b.Sterling Pipe & Tube, Inc. located in Toledo, Ohio:  On or about
September 6, 2006,
the employer did not ensure the 2K line 7.5 ton crane hook was equipped
with a safety
latch.
Among other methods, one feasible and acceptable method to correct this
hazard is to
ensure the crane hooks are functioning according to to ANSI B30.10-1999,
Hooks.
In accordance with 29 CFR 1903.19(c), abatement certification is required
for this
violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
  • — I (S) $750.00
  • — Z (S) $1375.00

5(a)(1)

Serious Gravity 03 2 instances 2 exposed
Issued
Dec 21, 2006
Abate by
Jan 4, 2007
Penalty
Initial $1,375 · Current $750 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees, in that the control
pendants for the 2X line crane and the 2K line crane were missing labels
which describe the
function of the control pendant buttons:
a.Sterling Pipe & Tube, Inc. located in Toledo, Ohio:  On or about
September 6, 2006,
the employer did not ensure the control pendant for the 2X line crane was
properly
labeled as to the function of the control pendant button. The control
pendant button for
the "north" function was not labeled.
b.Sterling Pipe & Tube, Inc. located in Toledo, Ohio:  On or about
September 6, 2006,
the employer did not ensure the control pendant for the 2K line crane was
properly
labeled as to the function of the control pendant buttons.  The control
pendant buttons
for the "north", "off", and "down" functions were not labeled.
Among other methods, one feasible and acceptable method to correct this
hazard is to
ensure the crane control pendants are labeled according to ANSI
B30.17-2003 "Overhead
and Gantry Cranes (Top Running Bridge, Single Girder, Underhung Hoist)".
In accordance with 29 CFR 1903.19(c), abatement certification is required
for this
violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
  • — I (S) $750.00
  • — Z (S) $1375.00

1910.179 L03 III

Serious Gravity 03 1 instance 2 exposed
Issued
Dec 21, 2006
Abate by
Jan 4, 2007
Recent events (2)
  • — I (S)
  • — Z (S)

5(a)(1)

Serious Gravity 02 1 instance 2 exposed
Issued
Dec 21, 2006
Abate by
Jan 4, 2007
Penalty
Initial $1,100 · Current $600 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees,
in that the control
pendant housing for the 2X line crane was damaged exposing employees to
electrical shock:
a.Sterling Pipe & Tube, Inc. located in Toledo, Ohio:  On or about
September 6, 2006,
the employer did not ensure the control pendant for the 2X line 5 ton
crane would not
expose exployes to electrical shock.
Among other methods, one feasible and acceptable method to correct this
hazard is to
ensure the crane pendant does not expose employees to electrical shock
according to
ANSI B30.17-2003 "Overhead and Gantry Cranes (Top Running Bridge, Single
Girder,
Underhung Hoist)".
In accordance with 29 CFR 1903.19(c), abatement certification is required
for this
violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (2)
  • — I (S) $600.00
  • — Z (S) $1100.00

1910.147 C06 I

Serious Gravity 03 1 instance 2 exposed
Issued
Dec 21, 2006
Abate by
Jan 4, 2007
Penalty
Initial $1,375 · Current $750 Reduced
Recent events (2)
  • — I (S) $750.00
  • — Z (S) $1375.00

View Sterling Pipe & Tube INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 309443471.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.