LA PORTE, TX ·
OSHA Inspection: OHMSTEDE LTD.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of OHMSTEDE LTD. in 12415 HWY. 225, LA PORTE, TX 77571 (NAICS 332410). OSHA activity number 310262506.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- OHMSTEDE LTD.
- Site address
- 12415 HWY. 225
- City
- LA PORTE
- State
- TX
- ZIP
- 77571
- Mailing
- P.O. BOX 817, LA PORTE, TX 77572
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (Y)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332410
- SIC code (legacy)
- 3443
- Employees
- 75
- Ownership type
- Private (A)
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Aug 17, 2007
- Abate by
- Sep 4, 2007
- Penalty
- Initial $1,875
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: the hazard of fire and explosion at the Ohmstede, La Porte facility on or about the date of May 6, 2007 at approximately 6:30 AM, while attempting to ignite the De-Coker Furnace. Among other methods, one feasible and acceptable abatement method to correct this hazard is prior to each furnace heating system startup, provisions shall be made for the removal of all flammable vapors and gases that have entered the heating chambers during the shutdown period as required under paragraph 8.4.1.1 and paragraph 8.9.1 of National Fire Protection Association NFPA 86, Standard for Ovens and Furnaces 2007 Edition. DISCLAIMERS:1)You are not limited to the abatement methods suggested above. 2)The methods explained are general and may not be effective in all cases. 3)The employer is responsible for selecting and carrying out an appropriate abatement method.nt
Recent events (2)
- · I (S)
- · Z (S) $1875.00
More inspections at Ohmstede LTD.
View Ohmstede LTD.'s full OSHA safety record →
More inspections in this industry (NAICS 332410)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 310262506.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.