OSHA Inspection: OHMSTEDE LTD.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of OHMSTEDE LTD. in 12415 HWY. 225, LA PORTE, TX 77571 (NAICS 332410). OSHA activity number 310262506.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ohmstede LTD. for free Get an email when a new federal OSHA severe-injury report for Ohmstede LTD. is published. One employer, no account, unsubscribe in one click.
Establishment
OHMSTEDE LTD.
Site address
12415 HWY. 225
City
LA PORTE
State
TX
ZIP
77571
Mailing
P.O. BOX 817, LA PORTE, TX 77572
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (Y)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332410
SIC code (legacy)
3443
Employees
75
Ownership type
Private (A)

1 citation on file for this inspection.

5(a)(1)

Deleted Serious Gravity 03 1 instance 3 exposed
Issued
Aug 17, 2007
Abate by
Sep 4, 2007
Penalty
Initial $1,875
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not furnish
employment and a place of employment which were free from recognized
hazards that were
causing or likely to cause death or serious physical harm to employees in
that employees were
exposed to:
the hazard of fire and explosion at the Ohmstede, La Porte facility on or
about the date
of May 6, 2007 at approximately 6:30 AM, while attempting to ignite the
De-Coker
Furnace.
Among other methods, one feasible and acceptable abatement method to
correct this
hazard is prior to each furnace heating system startup, provisions shall
be made for the
removal of all flammable vapors and gases that have entered the heating
chambers during
the shutdown period as required under paragraph 8.4.1.1 and paragraph
8.9.1 of National
Fire Protection Association NFPA 86, Standard for Ovens and Furnaces 2007
Edition.
DISCLAIMERS:1)You are not limited to the abatement methods suggested
above.
2)The methods explained are general and may not be
effective in all cases.
3)The employer is responsible for selecting and carrying out
an appropriate abatement method.nt
Recent events (2)
  • · I (S)
  • · Z (S) $1875.00

View Ohmstede LTD.'s full OSHA safety record →