CLEBURNE, TX —
OSHA Inspection: CRESTWOOD MIDSTREAM PARTNERS LP
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of CRESTWOOD MIDSTREAM PARTNERS LP in 2400 CR 326, CLEBURNE, TX 76033 (NAICS 211111). OSHA activity number 310440631.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CRESTWOOD MIDSTREAM PARTNERS LP
- Site address
- 2400 CR 326
- City
- CLEBURNE
- State
- TX
- ZIP
- 76033
- Mailing
- 801 CHERRY ST, SUITE 3700, UNIT 19, FORT WORTH, TX 76102
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 211111
- SIC code (legacy)
- 4922
- Employees
- 500
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Nov 20, 2007
- Abate by
- Dec 17, 2007
- Penalty
- Initial $4,500 · Current $4,500
General-duty citation text
SECTION 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: Explosion hazard when the Loveco 4-Burner Box Hot Oil Heater failed to light on a number of times. There were approximately 6 attempts to light the heater, when on the last attempt, the heater exploded. There was an excess amount of gas inside the box. The employer did not ensure that the box heater was equipped with the proper safety mechanisms to prevent such an explosion. Such safety mechanisms include but not limited to the following: alarms, sensors, pressure relief devices, and forced air vents. Also, the employer did not have a written standard operating procedure in place to handle situations to which a heater does not light. AMONG OTHER METHODS, ONE FEASIBLE AND ACCEPTABLE ABATEMENT METHOD TO CORRECT THE HAZARD IS: To ensure all heaters are equipped with the proper safety mechanisms to prevent an accumulation of hazardous atmospheres to avoid an explosion. Employer should follow the recommended practices/procedures in API for fired heaters. Such as but not limited to: API RP 556--Fired Heaters and Steam Generators and Std.560--Fired Heaters for General Refinery Service.
More inspections at Crestwood Midstream Partners LP
View Crestwood Midstream Partners LP's full OSHA safety record →
More inspections in this industry (NAICS 211111)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 310440631.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.