Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CRESTWOOD MIDSTREAM PARTNERS LP

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of CRESTWOOD MIDSTREAM PARTNERS LP in 2400 CR 326, CLEBURNE, TX 76033 (NAICS 211111). OSHA activity number 310440631.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Crestwood Midstream Partners LP — free Get an email when a new federal OSHA severe-injury report for Crestwood Midstream Partners LP is published. One employer, no account, unsubscribe in one click.
Site address
2400 CR 326
City
CLEBURNE
State
TX
ZIP
76033
Mailing
801 CHERRY ST, SUITE 3700, UNIT 19, FORT WORTH, TX 76102
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
211111
SIC code (legacy)
4922
Employees
500
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 8 exposed
Issued
Nov 20, 2007
Abate by
Dec 17, 2007
Penalty
Initial $4,500 · Current $4,500
SECTION 5(a)(1) of the Occupational Safety and Health Act of 1970:
The employer did not furnish employment and a place of employment which
were free from
recognized hazards that were causing or likely to cause death or serious
physical harm to
employees in that employees were exposed to:  Explosion hazard when the
Loveco 4-Burner
Box Hot Oil Heater failed to light on a number of times.  There were
approximately 6
attempts to light the heater, when on the last attempt, the heater
exploded.  There was an
excess amount of gas inside the box.  The employer did not ensure that the
box heater was
equipped with the proper safety mechanisms to prevent such an explosion.
Such safety
mechanisms include but not limited to the following:  alarms, sensors,
pressure relief
devices, and forced air vents. Also, the employer did not have a written
standard operating
procedure in place to handle situations to which a heater does not light.
AMONG OTHER METHODS, ONE FEASIBLE AND ACCEPTABLE ABATEMENT
METHOD TO CORRECT THE HAZARD IS:
To ensure all heaters are equipped with the proper safety mechanisms to
prevent
an
accumulation of hazardous atmospheres to avoid an explosion.  Employer
should follow the
recommended practices/procedures in API for fired heaters.  Such as but
not limited to:  API
RP 556--Fired Heaters and Steam Generators and Std.560--Fired Heaters for
General
Refinery Service.

View Crestwood Midstream Partners LP's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 310440631.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.