OSHA Inspection: KANSAS CITY POWER & LIGHT COMPANY

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of KANSAS CITY POWER & LIGHT COMPANY in 20250 NORTH 45 HIGHWAY, WESTON, MO 64098 (NAICS 221119). OSHA activity number 310932322.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Kansas City Power & Light Company — free Get an email when a new federal OSHA severe-injury report for Kansas City Power & Light Company is published. One employer, no account, unsubscribe in one click.
Site address
20250 NORTH 45 HIGHWAY
City
WESTON
State
MO
ZIP
64098
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221119
SIC code (legacy)
4911
Employees
130
Ownership type
A
Industry flags
Manufacturing safety.

3 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 10 1 instance 13 exposed
Issued
Nov 5, 2007
Abate by
Dec 8, 2007
Penalty
Initial $7,000
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to the hazard of steam burns while reacting to catastrophic
releases of steam:
Throughout the Iatan Station #1 the employer failed to develop emergency
procedures to address large steam releases.  Employees were exposed to
serious
burns while reacting to a catastrophic steam line failure.  Among other
methods,
one feasible and acceptable abatement method to correct the hazardous
condition
would be to implement operating procedures and training to address the
emergency conditions as described in the National Fire Protection
Association
(NFPA) Boiler and Combustion Systems Hazard Code 85 - 2007 Edition.
Abatement certification is required for this item (using the CERTIFICATION
OF
CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating
that
abatement is complete must be included with your certification.  This
documentation may
include, but is not limited to, evidence of the purchase or repair of
equipment, photographic or
video evidence of abatement, or other written records.
Recent events (2)
  • — F (S)
  • — Z (S) $7000.00

5(a)(1)

Serious Gravity 10 1 instance 13 exposed
Issued
Nov 5, 2007
Abate by
Dec 8, 2007
Penalty
Initial $7,000 · Current $700 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to the hazard of steam burns due to potential power piping
rupture occurrence:
At Iatan Station #1 the operating company had not determined the root
cause of
a steam line rupture in order to develop corrective action to minimize the
probability of recurrence in that no consideration was given to factors
such as,
but not limited to, original pipe design requirements and implied
corrosion
limits.
Among other methods, one feasible and acceptable abatement method to
correct
the hazardous condition would be to generate a failure report as described
in the
American Society of Mechanical Engineers (ASME) Code for Pressure Piping
B31.1 - 2004 Edition.
Abatement certification is required for this item (using the CERTIFICATION
OF
CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating
that
abatement is complete must be included with your certification.  This
documentation may
include, but is not limited to, evidence of the purchase or repair of
equipment, photographic or
video evidence of abatement, or other written records.
Recent events (2)
  • — F (S) $700.00
  • — Z (S) $7000.00

5(a)(1)

Deleted Serious Gravity 10 1 instance 10 exposed
Issued
Nov 5, 2007
Abate by
Dec 8, 2007
Penalty
Initial $7,000
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees
in that employees
were exposed to the hazard of steam burns due to inadequate inspection and
maintenance of high
pressure high temperature water piping systems:
In that throughout the power station employees were exposed to
the hazard of serious burns from high pressure high temperature
water lines which were not adequately inspected nor properly
maintained.  Among other methods, one feasible and acceptable
abatement method to correct this hazardous condition would be to
implement a written routine, periodic inspection protocol on all
components of high pressure high temperature water piping
system(s) including, but not limited to, supporting elements (i.e.
anchors and supports) and piping erosion/corrosion monitoring as
described in American Society of Mechanical Engineers (ASME)
Code for Pressure Piping B31.1 - 2004 Edition.
Abatement certification is required for this item (using the CERTIFICATION
OF
CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating
that
abatement is complete must be included with your certification.  This
documentation may
include, but is not limited to, evidence of the purchase or repair of
equipment, photographic or
video evidence of abatement, or other written records.
Recent events (2)
  • — F (S)
  • — Z (S) $7000.00

View Kansas City Power & Light Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 310932322.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.