Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ARIZONA CHEMICAL CO.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ARIZONA CHEMICAL CO. in 1201 W. LATHROP AVE., SAVANNAH, GA 31401 (NAICS 325191). OSHA activity number 310991963.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Arizona Chemical CO. — free Get an email when a new federal OSHA severe-injury report for Arizona Chemical CO. is published. One employer, no account, unsubscribe in one click.
Site address
1201 W. LATHROP AVE.
City
SAVANNAH
State
GA
ZIP
31401
Mailing
PO BOX 2028, SAVANNAH, GA 31402
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325191
SIC code (legacy)
2861
Employees
216
Ownership type
A

2 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 10 exposed
Issued
May 15, 2009
Abate by
May 20, 2009
Penalty
Initial $4,500 · Current $4,500
P.L. 91-596 Section 5(a)(1) of the Occupational Safety and Health Act of
1970: The employer
did not furnish employment and a place of employment which were free from
recognized hazards
that were causing or likely to cause death or serious physical harm to
employees in that
employees were exposed to the hazard(s) of combustion, explosion, and fire
hazard:
a)Back of Package Boiler (Platform Area) - On or about January 21, 2009, a
natural gas vent was installed close the floor of a leased package boiler
platform
exposing employees to combustion, explosion, and fire hazards.
A feasible means of abatement would be to construct a natural gas vent in
accordance with NFPA 85, Boiler and Combustion Systems Hazards Code 2007
edition, where the natural gas discharge area is above and/or away from
areas
where employees work and/or where ignition sources could be present.

1910.37 A02

Serious Gravity 10 1 instance 7 exposed
Issued
May 15, 2009
Abate by
Jun 11, 2009
Penalty
Initial $4,500 · Current $4,500

View Arizona Chemical CO.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 310991963.