MOMENCE, IL —
OSHA Inspection: GILSTER MARY LEE
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of GILSTER MARY LEE in 305 W. WASHINGTON STREET, MOMENCE, IL 60954 (NAICS 311330). OSHA activity number 312595895.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GILSTER MARY LEE
- Site address
- 305 W. WASHINGTON STREET
- City
- MOMENCE
- State
- IL
- ZIP
- 60954
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311330
- SIC code (legacy)
- 2066
- Employees
- 70
- Ownership type
- A
- Industry flags
- Manufacturing health.
Citations
18 citations on file for this inspection.
5(a)(1)
- Issued
- Oct 5, 2009
- Abate by
- Jun 15, 2010
- Penalty
- Initial $5,000 · Current $2,000 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were likely to cause death or serious physical harm in that employees were exposed to the hazard of potential fire and explosion, including serious physical harm, severe burns, blunt force trauma and possibly death from the improper design and maintenance of the production processes involving cocoa powder, sugar and other dusts: Employees were not adequately protected against fire and explosion hazard in that: Production areas: Can line/mixer room #1, mixer room# 2, mixer room #3, cloud line (packaging line), syrup line, and dryer room: (1) Seven dust collectors greater than 8 cubic feet each were located inside the building. The dust collectors lacked recognized fire/explosion controls (e.g. containment, suppression, inerting, venting, etc.) required for safe operation. (2) Equipment connected via ductwork including, but not limited to, dust collectors, instantizer, hoppers, bins, silos, bucket elevators, screw augers, pneumatic conveying systems and a belt conveyor were not equipped with isolation methods to prevent propagation of an explosion. (3) Lack of an ignition control program. (4) Packaging and weighing systems were not all equipped with venting systems or air aspiration devices to collect the dust emitted by rapid air displacement during filling and emptying. (5) Lack of established procedures or an automatic sequence to shut down related to machinery if the dust collection system shuts down during operations. (6) Combustible dust which leaked from various equipment was not eliminated or removed concurrent with operations. ABATEMENT NOTE: Among other methods, one feasible and acceptable abatement method to correct these hazards is to comply with National Fire Protection Agency (NFPA) 61 "Standard for the Prevention of Fire and Dust Explosions in Agricultural and Food Processing Facilities: (2008) Edition and NFPA 69 "Standard on Explosion Prevention Systems" 2008 Edition; including but not limited to: a)Relocate dust collectors outdoors and/or safely vent to an unoccupied location. b)Install explosion prevention and/or protection for all dust collectors, instantizer, hoppers, bins, silos, bucket elevators, screw augers, pneumatic conveying systems, and belt conveyors. c)Install isolation methods which would prevent the propagation between pieces of equipmentconnected by ductwork. d)Ensure that an effective ignition control program was implemented which addressed bonding and grounding, hot surfaces, or friction heat from various transfer methods. e)Ensure that all electrical equipment is listed for use in a Class II, Group G, Division I or II area. f)Equip packaging and weighing systems with venting systems or air aspiration to collect dust emitted by rapid air displacement. g)Establish procedures which include a sequence to shut down related equipment if dust collection system(s) shut down. h)Eliminate dust leaks from equipment and/or ensure removal of the dust concurrent with operations. NOTE: 29 CFR 1903.19 REQUIRES THAT YOU PROVIDE CERTIFICATION AND DOCUMENTATION OF ABATEMENT FOR THIS ITEM.
Recent events (2)
- — I (S) $2000.00
- — Z (S) $5000.00
1910.22 A01
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
- Penalty
- Initial $5,000 · Current $2,000 Reduced
Recent events (2)
- — I (S) $2000.00
- — Z (S) $5000.00
1910.23 C01
- Issued
- Oct 5, 2009
- Abate by
- Oct 8, 2009
- Penalty
- Initial $5,000 · Current $2,000 Reduced
Recent events (2)
- — I (S) $2000.00
- — Z (S) $5000.00
1910.95 D01
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
- Penalty
- Initial $3,500 · Current $1,500 Reduced
Recent events (2)
- — I (S) $1500.00
- — Z (S) $3500.00
1910.95 I02 I
- Issued
- Oct 5, 2009
- Abate by
- Oct 9, 2009
1910.95 I02 IIA
- Issued
- Oct 5, 2009
- Abate by
- Oct 16, 2009
1910.95 M01
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
1910.134 C
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
- Penalty
- Initial $5,000 · Current $2,000 Reduced
Recent events (2)
- — I (S) $2000.00
- — Z (S) $5000.00
1910.134 D01 III
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
1910.134 E01
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
1910.134 F01
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
1910.134 K01
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
1910.146 C04
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
- Penalty
- Initial $2,500 · Current $1,000 Reduced
Recent events (2)
- — I (S) $1000.00
- — Z (S) $2500.00
1910.212 A01
- Issued
- Oct 5, 2009
- Abate by
- Oct 16, 2009
- Penalty
- Initial $2,500 · Current $1,000 Reduced
Recent events (2)
- — I (S) $1000.00
- — Z (S) $2500.00
1910.307 B
- Issued
- Oct 5, 2009
- Abate by
- Jun 15, 2010
- Penalty
- Initial $5,000 · Current $2,000 Reduced
Recent events (2)
- — I (S) $2000.00
- — Z (S) $5000.00
1910.1000 A02
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
- Penalty
- Initial $5,000 · Current $1,500 Reduced
Recent events (2)
- — I (S) $1500.00
- — Z (S) $5000.00
1910.1000 E
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
1910.132 D01
- Issued
- Oct 5, 2009
- Abate by
- Nov 23, 2009
More inspections at Gilster Mary LEE
View Gilster Mary LEE's full OSHA safety record →
More inspections in this industry (NAICS 311330)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 312595895.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.