Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: TOM WENTE D/B/A T & L LOCKER SERVICE

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of TOM WENTE D/B/A T & L LOCKER SERVICE in S RR.32, STEWARDSON, IL 62463 (NAICS 311612). OSHA activity number 312891112.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch TOM Wente D/B/A T & L Locker Service for free Get an email when a new federal OSHA severe-injury report for TOM Wente D/B/A T & L Locker Service is published. One employer, no account, unsubscribe in one click.
Site address
S RR.32
City
STEWARDSON
State
IL
ZIP
62463
Mailing
SOUTH ROUTE 32, BOX 13A, STEWARDSON, IL 62463
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311612
SIC code (legacy)
2013
Employees
11
Ownership type
A

5 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 3 instances 10 exposed
Issued
Apr 5, 2010
Abate by
Jul 30, 2010
Penalty
Initial $1,500 · Current $900 Reduced
c.Install dedicated mechanical ventilation and associated make-up air
sufficient to
prevent accumulation of ammonia in the space in the event of a leak.
(Section 8.11.4
and 8.11.5)
d.Remove all combustion equipment, like the natural gas powered water
heater, from
the space.  (Section 8.11.6)
e.Provide legible permanent signs, securely attached and easily
accessible, reading
"Machinery Room - Authorized Personnel Only", communicating that entry is
forbidden except by personnel trained in emergency procedures invoked by
activation
of the ammonia alarm.  (Section 8.11.8)
f.Replace the ceiling of the space with noncombustible construction
(Section 8.12).
h.Tightly seal pipes piercing the interior walls of the machinery room to
the walls
through which they pass.  (Section 8.12)
i.Provide remote control of the mechanical equipment in the refrigerating
machinery
room, immediately outside the machinery room door, solely for the purpose
of
shutting down the equipment in an emergency.  (Section 8.12)
***Abatement documentation is required for this item in accordance with the
requirements of 29 CFR 1903.19(d)***
Recent events (2)
  • · I (S) $900.00
  • · Z (S) $1500.00

1910.22 A01

Serious Gravity 03 1 instance 10 exposed
Issued
Apr 5, 2010
Abate by
Apr 29, 2010
Penalty
Initial $750 · Current $400 Reduced
Recent events (2)
  • · I (S) $400.00
  • · Z (S) $750.00

1910.37 A02

Deleted Serious Gravity 03 1 instance 10 exposed
Issued
Apr 5, 2010
Abate by
May 20, 2010
Penalty
Initial $750 · Current $750
Recent events (2)
  • · I (S) $750.00
  • · Z (S) $750.00

1910.120 Q01

Serious Gravity 10 1 instance 10 exposed
Issued
Apr 5, 2010
Abate by
May 20, 2010
Penalty
Current $450
Recent events (2)
  • · I (S) $450.00
  • · Z (S)

1910.307 C

Serious Gravity 03 1 instance 10 exposed
Issued
Apr 5, 2010
Abate by
May 20, 2010
Penalty
Initial $750 · Current $450 Reduced
Recent events (2)
  • · I (S) $450.00
  • · Z (S) $750.00

View TOM Wente D/B/A T & L Locker Service's full OSHA safety record →