STEWARDSON, IL ·
OSHA Inspection: TOM WENTE D/B/A T & L LOCKER SERVICE
Follow-up inspection · Safety discipline
At a glance
On , OSHA opened a follow-up safety inspection of TOM WENTE D/B/A T & L LOCKER SERVICE in S RR.32, STEWARDSON, IL 62463 (NAICS 311612). OSHA activity number 314851940.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TOM WENTE D/B/A T & L LOCKER SERVICE
- Site address
- S RR.32
- City
- STEWARDSON
- State
- IL
- ZIP
- 62463
- Mailing
- SOUTH ROUTE 32, BOX 13A, STEWARDSON, IL 62463
What kind of inspection was it?
- Inspection type
- Follow-up (F)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311612
- SIC code (legacy)
- 2013
- Employees
- 10
- Ownership type
- A
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Mar 30, 2012
- Abate by
- Aug 30, 2012
- Penalty
- Initial $3,300 · Current $1,500 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment that were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees, in that employees were exposed to toxic anhydrous ammonia inhalation hazards in the event of an uncontrolled release originating from the ammonia machinery room: Machinery room - On or about November 8, 2011, employees were not adequately protected against the potential release of anhydrous ammonia in that: a)The machinery room was not isolated from other work areas to prevent the migration of anhydrous ammonia b)There was not sufficient means to warn employees working throughout the facility in the event of an ammonia release Among other methods, feasible and acceptable methods to control these hazards are to adhere to the safe design, installation, and operation of anhydrous ammonia refrigeration systems as prescribed by ANSI/ASHRAE 15-2007, "Safety Standard for Refrigeration Systems", specifically: a.Separate the space containing the refrigeration machinery from other occupancies by tight construction with tight fitting, self-closing fire doors. (Section 8.11.2) b.Install an ammonia detector set to alarm at a value not greater than the American Conference of Governmental Industrial Hygienist (ACGIH), Threshhold Limit Value (TLV), time-weighted average (TWA) (currently 35 ppm) and that actuates a visual and audible alarm that warns both inside and outside each entrance to the machinery room. (Section 8.11.2.1) c.Provide legible permanent signs, securely attached and easily accessible, reading "Machinery Room - Authorized Personnel Only", communicating that entry is forbidden except by personnel trained in emergency procedures invoked by activation of the ammonia alarm. (Section 8.11.8) d.Tightly seal pipes piercing the interior walls of the machinery room to the walls, ceiling or floor through which they pass. (Section 8.12) e.Install equipment to provide inlet air to replace that being exhausted. (Section 8.11.4) f.Ensure there is no airflow to or from an occupied space through a machinery room unless the air is ducted and sealed in such a manner as to prevent any refrigerant leakage from entering the airstream. (Section 8.11.7) ***Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c)***
Recent events (2)
- · I (S) $1500.00
- · Z (S) $3300.00
1910.307 C
- Issued
- Mar 30, 2012
- Abate by
- Aug 30, 2012
- Penalty
- Initial $5,000 · Current $2,500 Reduced
Recent events (2)
- · I (R) $2500.00
- · Z (R) $5000.00
More inspections at TOM Wente D/B/A T & L Locker Service
View TOM Wente D/B/A T & L Locker Service's full OSHA safety record →
More inspections in this industry (NAICS 311612)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 314851940.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.