OAK CREEK, WI ·
OSHA Inspection: AZCO INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of AZCO INC. in 11050 S. CHICAGO RD. ELM ROAD GEN. STATION UNIT #1, OAK CREEK, WI 53154 (NAICS 237990). OSHA activity number 313524548.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AZCO INC.
- Site address
- 11050 S. CHICAGO RD. ELM ROAD GEN. STATION UNIT #1
- City
- OAK CREEK
- State
- WI
- ZIP
- 53154
- Mailing
- P.O. BOX 567, APPLETON, WI 54912
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (Y)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237990
- SIC code (legacy)
- 1629
- Employees
- 10
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Jan 20, 2010
- Abate by
- Feb 22, 2010
- Penalty
- Initial $1,875 · Current $1,875
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that workers were exposed to hazards associated with dust explosion, deflagration, or other fire hazards within a permit required confined space: (a)At the Elm Road Generating Station Unit 1 site, on November 24, 2009, AZCO Inc. allowed two employees to enter Pulverizer E, a permit required confined space, using the entry permit system required by the general contractor and: (1)Allowed employees to work in the space despite changing work conditions that introduced combustible coal dust into the space; (2)In the event of a fire or explosion, did not have a means of accounting for which of their employees were working in the space. Among other feasible methods, one feasible and acceptable means of abatement would be to comply with ANSI/ASSE Z117.1-2009 Safety Requirements for Confined Spaces, and (1) Immediately remove employees from a permit required confined space whenever hazards are encountered or created during the course of an entry permit (in accordance with section 5.5 of ANSI/ASSE Z117.1); (2) Inform the general contractor immediately whenever hazards are encountered or created during the course of an entry permit (in accordance with section 11.5 of ANSI/ASSE Z117.1); and (3) Coordinate with the general contractor so all entrants into permit required confined spaces are accounted for (in accordance with section 5.1.1 of ANSI/ASSE Z117.1). Certification, with date and method of abatement required. Certification of abatement is required by 29 CFR Part 1903 and is to be submitted within ten (10) calendar days after the abatement date.ment
Recent events (2)
- · F (S) $1875.00
- · Z (S) $1875.00
1926.403 B02
- Issued
- Jan 20, 2010
- Abate by
- Jan 26, 2010
- Penalty
- Initial $1,875 · Current $950 Reduced
Recent events (2)
- · F (O) $950.00
- · Z (S) $1875.00
More inspections at Azco INC.
View Azco INC.'s full OSHA safety record →
More inspections in this industry (NAICS 237990)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 313524548.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.