PAULSBORO, NJ —
OSHA Inspection: COIM USA INC
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of COIM USA INC in 286 MANUTA GROVE RD, PAULSBORO, NJ 08066 (NAICS 325520). OSHA activity number 315860635.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COIM USA INC
- Site address
- 286 MANUTA GROVE RD
- City
- PAULSBORO
- State
- NJ
- ZIP
- 08066
- Mailing
- 286 MANUTA GROVE RD, WEST DEPTFORD, NJ 08066
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325520
- SIC code (legacy)
- 2891
- Employees
- 70
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.22 A02
- Issued
- Nov 8, 2011
- Abate by
- Dec 2, 2011
- Penalty
- Initial $2,550 · Current $1,911 Reduced
General-duty citation text
29 CFR 1910.22 (a)(2) The floor of every workroom was not maintained in a clean and, so far as possible, a dry condition. a) Adhesives plant: The first and second floors of the plant near the reactors had chemicals on the floor and was not kept clean and dry, on or about 10/3/11. b) Polyester plant: The first floor of the plant near the reactors and dissolvers had chemicals on the floor and was not kept clean and dry, on or about 10/3/11. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $1911.00
- — Z (S) $2550.00
1910.23 A02
- Issued
- Nov 8, 2011
- Abate by
- Nov 11, 2011
- Penalty
- Initial $2,550 · Current $1,913 Reduced
General-duty citation text
29 CFR 1910.23 (a)(2) Every ladderway floor opening or platform was not guarded by a standard railing with standard toeboard on all exposed sides (except at entrance to opening), with the passage through the railing either provided with a swinging gate or so offset that a person could not walk directly into the opening. a) Polyester production plant between finishers: A swinging gate with a standard railing was not provided at the entrance to the waste pit, on or about 10/3/11.
Recent events (2)
- — I (S) $1913.00
- — Z (S) $2550.00
1910.23 C01
- Issued
- Nov 8, 2011
- Abate by
- Dec 2, 2011
General-duty citation text
29 CFR 1910.23 (c)(1) Open-sided floors or platforms 4 feet or more above adjacent floor or ground level were not guarded by a standard railing (or the equivalent as specified in paragraph (e)(3) of this section) on all open sides except where there is entrance to a ramp, stairway, or fixed ladder. a) Polyester plant tank truck filling platform: Employees filling tankers with chemicals stood on top of the trucks approximately 15 feet above the ground, without fall protection, on or about 10/3/11. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S)
- — Z (S)
1910.106 E06 II
- Issued
- Nov 8, 2011
- Abate by
- Nov 11, 2011
- Penalty
- Initial $3,400 · Current $2,551 Reduced
General-duty citation text
29 CFR 1910.106 (e)(6)(ii) Class I liquids were not dispensed into containers where the nozzle and container were electrically interconnected: a) Warehouse building 2: Employees did not bond a 55-gallon drum to a safety can when emptying solvent waste, on or about 10/12/11. b) Warehouse building 2: Employees did not bond a pump on a 55-gallon drum to a safety can when filling the cans with acetone, on or about 10/12/11.
Recent events (2)
- — I (S) $2550.50
- — Z (S) $3400.00
1910.147 C04 I
- Issued
- Nov 8, 2011
- Abate by
- Jan 20, 2012
- Penalty
- Initial $3,400 · Current $2,551 Reduced
General-duty citation text
29 CFR 1910.147 (f)(3)(ii)(D) Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in the activities covered by this section. a) Polyester plant: Written procedures for lockout tagout did not include such information as, but not limited to, the specific energy sources, the specific methods to control the energy sources,the sequence of activities required to control the hazards, the location of the isolation devices used, how is stored energy in the system released, the necessity for air monitoring equipment and methods to test the system to determine de-energization, on or about 10/12/11. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $2550.50
- — Z (S) $3400.00
1910.147 F03 IID
- Issued
- Nov 8, 2011
- Abate by
- Jan 20, 2012
General-duty citation text
29 CFR 1910.147 (f)(3)(ii)(D) Each authorized employee did not affix a personal lockout or tagout device to the group lockout device, group lockbox, or comparable mechanism when he or she began work. a) Polyester plant: Each authorized employee did not apply a personal lock to a group lockout device when servicing the diothermic hot oil pump for reactor one, on or about 10/12/11. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S)
- — Z (S)
1910.305 G01 IVA
- Issued
- Nov 8, 2011
- Abate by
- Dec 2, 2011
- Penalty
- Initial $2,550 · Current $1,913 Reduced
General-duty citation text
29 CFR 305 (g)(1)(iv)(A) Flexible cords and cables were used as a substitute for the fixed wiring of a structure: a) Building three quality control lab: A VWR hotplate and a Thermo Scientific Super Nova Multiplace heater were powered by a power strip, on or about 10/12/11. b) Warehouse building two research lab "one gallon hood": Mettler Toledo and VWR hot plates were powered by a power strip, on or about 10/12/11. c) Warehouse building two research lab "five gallon hood": IKA mixers were powered by power strips, on or about 10/12/11. d) Warehouse building two boiler room: An extension cord was used to power a pump that operated a chiller, on or about 10/12/11. e) Warehouse building two quality control pre-polymer applications lab: A power strip was used to power a heat gun used with the distillation unit, on or about 10/12/11. f) Warehouse building two quality control pre-polymer applications lab: An extension cord was used to power a power strip that operated a distillation unit, on or about 10/12/11. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $1913.00
- — Z (S) $2550.00
1910.146 C02
- Issued
- Nov 8, 2011
- Abate by
- Nov 11, 2011
General-duty citation text
29 CFR 1910.146 (c)(2) When the workplace contained permit spaces, the employer did not inform exposed employees, by posting danger signs or by any other equally effective means, of the existence and location of and the danger posed by the permit spaces. a) Polyester production plant between finishers: The employer did not post a confined space sign at the waste pit that the employees enter to clean, on or about 10/3/11.
Recent events (2)
- — I (O)
- — Z (O)
1910.147 C06 II
- Issued
- Nov 8, 2011
- Abate by
- Dec 2, 2011
General-duty citation text
29 CFR 1910.147 (c)(6) The employer did not certify that the periodic inspections were performed. The certification did not identify the machine or equipment on which the energy control procedure was being utilized, the date of the inspection, the employees included in the inspection, and the person performing the inspection. a) Throughout facility: The employer did not certify that periodic inspections were completed for the energy control procedures, on or about 10/3/11. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (O)
- — Z (O)
More inspections at Coim USA INC
View Coim USA INC's full OSHA safety record →
More inspections in this industry (NAICS 325520)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 315860635.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.