ROSEBURG, OR —
OSHA Inspection: VA ROSEBURG MEDICAL CENTER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of VA ROSEBURG MEDICAL CENTER in 913 NW GARDEN VALLEY BOULEVARD, ROSEBURG, OR 97470 (NAICS 622110). OSHA activity number 330968694.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VA ROSEBURG MEDICAL CENTER
- Site address
- 913 NW GARDEN VALLEY BOULEVARD
- City
- ROSEBURG
- State
- OR
- ZIP
- 97470
- Mailing
- 913 NW GARDEN VALLEY BOULEVARD, ROSEBURG, OR 97470
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 778
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.101 B
- Issued
- Dec 13, 2011
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): Section 3.3.5, Compressed Gas Association pamphlet P-1-1965, as adopted by 29 CFR 1910.101(b): The storage room for compressed gas cylinders was not well ventilated: a) In Building 1, Floor 5, in the Oxygen Storage Room, on or about July 19, 2011 and at times prior thereto, mechanical exhaust ventilation inside the oxygen storage room was not operable.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 F03 I
- Issued
- Dec 13, 2011
- Abate by
- Jan 12, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(f)(3)(i): When servicing and/or maintenance was performed by a crew, craft, department or other group, they did not utilize a procedure which afforded the employees a level of protection equivalent to that provided by the implementation of a personal lockout or tagout device, e.g. a group lockout or tagout procedure. a) In the Boiler Plant, in the lockout procedure for boilers where numerous employees conducted work, the written procedure did not require the use of locks and the procedure did not require the use of individual lockout/tagout devices by each authorized employee.
Recent events (1)
- — Z (S) $0
1910.147 F03 II D
- Issued
- Dec 13, 2011
- Abate by
- Jan 12, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(f)(3)(ii)(D): Each authorized employee did not affix a personal lockout or tagout device to a group lockout device, group lockbox, or comparable mechanism when he or she began work, and remove those devices when he or she stopped work on the machine or equipment being serviced or maintained. a) In the Boiler Plant maintenance employees did not use locks that were labeled to identify the specific employee authorized to apply and remove the lock. The lockout/tagout procedure for the boilers did not utilize a group lockout device, a group lockbox or any comparable mechanism.
Recent events (1)
- — Z (S) $0
1910.303 B01
- Issued
- Dec 13, 2011
- Abate by
- Jan 12, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: a) In Room A402, Blood Gas Lab, an electrical receptacle outlet within three feet of the sink was not equipped with a ground-fault-circuit-interrupter; b) In the Dental Clinic, Entry Way, Front Room, an electrical receptacle outlet within three feet of the sink was not equipped with a ground-fault-circuit-interrupter; c) In the Kitchen, in Ingredients Control, two electrical receptacle outlets within 20 inches to 30 inches of the sink were not equipped with ground-fault-circuit-interrupters.
Recent events (1)
- — Z (S) $0
1910.37 B02
- Issued
- Dec 13, 2011
- Abate by
- Jan 12, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not marked by a sign reading "Exit": a) In the Pharmacy, IV Room the designated exit door was not equipped with an exit sign; b) In the Short Stay Area the door across A401A and the main door were not equipped with exit signs.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at VA Roseburg Medical Center
View VA Roseburg Medical Center's full OSHA safety record →
More inspections in this industry (NAICS 622110)
More inspections in OR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 330968694.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.