OSHA Inspection: VA ROSEBURG MEDICAL CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of VA ROSEBURG MEDICAL CENTER in 913 NW GARDEN VALLEY BOULEVARD, ROSEBURG, OR 97470 (NAICS 622110). OSHA activity number 330968694.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch VA Roseburg Medical Center — free Get an email when a new federal OSHA severe-injury report for VA Roseburg Medical Center is published. One employer, no account, unsubscribe in one click.
Site address
913 NW GARDEN VALLEY BOULEVARD
City
ROSEBURG
State
OR
ZIP
97470
Mailing
913 NW GARDEN VALLEY BOULEVARD, ROSEBURG, OR 97470
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
778
Ownership type
D

5 citations on file for this inspection.

1910.101 B

Deleted Serious Gravity 1 1 instance 10 exposed
Issued
Dec 13, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.101(b):     Section 3.3.5, Compressed Gas Association pamphlet P-1-1965, as adopted by 29 CFR 1910.101(b): The storage room for compressed gas cylinders was not well ventilated:    a)   In Building 1, Floor 5,  in the Oxygen Storage Room, on or about July 19, 2011 and at times prior thereto, mechanical exhaust ventilation inside the oxygen storage room was not operable.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 F03 I

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 13, 2011
Abate by
Jan 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(f)(3)(i):     When servicing and/or maintenance was performed by a crew, craft, department or other group, they did not utilize a procedure which afforded the employees a level of protection equivalent to that provided by the implementation of a personal lockout or tagout device, e.g. a group lockout or tagout procedure.    a)  In the Boiler Plant, in the lockout procedure for boilers where numerous employees conducted work, the written procedure did not require the use of locks and the procedure did not require the use of individual lockout/tagout devices by each authorized employee.
Recent events (1)
  • — Z (S) $0

1910.147 F03 II D

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 13, 2011
Abate by
Jan 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(f)(3)(ii)(D):     Each authorized employee did not affix a personal lockout or tagout device to a group lockout device, group lockbox, or comparable mechanism when he or she began work, and  remove those devices when he or she stopped work on the machine or equipment being serviced or maintained.    a)  In the Boiler Plant maintenance employees did not use locks that were labeled to identify the specific employee authorized to apply and remove the lock.  The lockout/tagout procedure for the boilers did not utilize a group lockout device, a group lockbox or any comparable mechanism.
Recent events (1)
  • — Z (S) $0

1910.303 B01

Serious Gravity 5 4 instances 10 exposed
Issued
Dec 13, 2011
Abate by
Jan 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(1):     Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:    a)  In Room A402, Blood Gas Lab, an electrical receptacle outlet within three feet of the sink was not equipped with a ground-fault-circuit-interrupter;    b)  In the Dental Clinic, Entry Way, Front Room, an electrical receptacle outlet within three feet of the sink was not equipped with a ground-fault-circuit-interrupter;    c)  In the Kitchen, in Ingredients Control, two electrical receptacle outlets within 20 inches to 30 inches of the sink were not equipped with ground-fault-circuit-interrupters.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Deleted Other-than-serious 3 instances 1 exposed
Issued
Dec 13, 2011
Abate by
Jan 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2):     Each exit was not marked by a sign reading "Exit":    a)  In the Pharmacy, IV Room the designated exit door was not equipped with an exit sign;    b)  In the Short Stay Area the door across A401A and the main door were not equipped with exit signs.