OSHA Inspection: OREGON ARMY NATIONAL GUARD, USPFO, LOGISTICS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of OREGON ARMY NATIONAL GUARD, USPFO, LOGISTICS in 15300 INDUSTRIAL WAY BUILDING 6550, CLACKAMAS, OR 97015 (NAICS 493110). OSHA activity number 330969056.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Oregon Army National Guard, Uspfo, Logistics — free Get an email when a new federal OSHA severe-injury report for Oregon Army National Guard, Uspfo, Logistics is published. One employer, no account, unsubscribe in one click.
Site address
15300 INDUSTRIAL WAY BUILDING 6550
City
CLACKAMAS
State
OR
ZIP
97015
Mailing
15300 INDUSTRIAL WAY, CLACKAMAS, OR 97015
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
40
Ownership type
D

4 citations on file for this inspection.

1910.304 F01 V

Serious Gravity 5 1 instance 9 exposed
Issued
Sep 12, 2011
Abate by
Oct 11, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(v):     Fuses and circuit breakers for circuits rated 600 volts, nominal, or less were not located or shielded so that employees would not be burned or otherwise injured by their  operation.      (a) Located in the SE corner of the warehouse, circuit breaker panel MDP did not have a door to provide shielding in the event of a ciruit breaker malfunction.
Recent events (1)
  • — Z (S) $0

1904.40 A

Other-than-serious 39 exposed
Issued
Sep 12, 2011
Abate by
Oct 11, 2011
Penalty
Initial $0 · Current $0
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours.    (a) Located at the Oregon Army National Guard USPFO at Camp Withycombe, on or about July 29, 2011, the employer failed to provide copies of the injury and illness records to an authorized representative. OSHA 300 logs and OSHA 300a summary pages were never provided for 2008, 2009, and 2010. The OSHA 300 log for 2011 also was not provided.
Recent events (1)
  • — Z (O) $0

1910.178 A05

Other-than-serious 9 exposed
Issued
Sep 12, 2011
Abate by
Oct 11, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.178(a)(5):     When trucks are equipped with front-end attachments other than factory installed attachments, it was not requested that the truck be marked to identify the attachments and show the approximate weight of the truck and attachment combination at maximum elevation with load laterally centered.      (a) Located in the USPFO warehouse at Camp Withycombe, a US Army Hyster forklift WJ04T3 was available for use with 6' fork extensions, but the forklift was not marked to indicate the approximate weight of the truck and attachment combination at maximum elevation with load laterally centered.
Recent events (1)
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 9 exposed
Issued
Sep 12, 2011
Abate by
Oct 11, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii):     The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:          (a) Located in the SE corner of the USPFO warehouse at Camp Withycombe, electrical panel MDP had mops and a broom stored in front of it.
Recent events (1)
  • — Z (O) $0

View Oregon Army National Guard, Uspfo, Logistics's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 330969056.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.