OSHA Inspection: INEOS USA LLC

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of INEOS USA LLC in 1900 FORT AMANDA ROAD, LIMA, OH 45804 (NAICS 325199). OSHA activity number 330973611.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ineos USA LLC — free Get an email when a new federal OSHA severe-injury report for Ineos USA LLC is published. One employer, no account, unsubscribe in one click.
Establishment
INEOS USA LLC
Site address
1900 FORT AMANDA ROAD
City
LIMA
State
OH
ZIP
45804
Mailing
1900 FORT AMANDA ROAD, LIMA, OH 45804
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325199
Employees
35
Ownership type
A

3 citations on file for this inspection.

1910.119 F04

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 2, 2011
Abate by
Jan 31, 2012
Penalty
Initial $3,750 · Current $3,750
29 CFR 1910.119(f)(4):  The employer did not develop and implement safe work practices to provide for the control of hazards during operations such as lockout/tagout; confined space entry; opening process equipment or piping; and control over entrance into a facility by maintenance, contractor, laboratory, or other support personnel.  These safe work practices shall apply to employees and contractor employees.    a. Ineos USA LLC located in Lima, Ohio:  On or about July 14, 2011, the employer did not ensure the operator for the purification section field verified with each authorized employee, where the lockout points were located on the spare steam reboiler prior to the authorized employees applying lockout devices to the lockout board. This resulted in approximately 3500 gallons of acrylonitrile being released due to the wrong process line being opened.     In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
  • — I (S) $3750
  • — Z (S) $3750

1910.147 D06

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 2, 2011
Abate by
Jan 31, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(d)(6): Verification of isolation.  Prior to starting work on machines or equipment that have been locked out or tagged out, the authorized employee did not verify that isolation and deenergization of the machine or equipment had been accomplished.    a. Ineos USA LLC located in Lima, Ohio:  On or about July 14, 2011, the employer did not ensure that the operator for the purification section field verified with each authorized employee, the location of the lockout points on the spare steam reboiler prior to the authorized employees applying lockout devices to the lockout board.  This resulted in approximately 3500 gallons of acrylonitrile being released due to the wrong process line being opened.       In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C06 I

Deleted Serious Gravity 5 1 instance 5 exposed
Issued
Dec 2, 2011
Abate by
Dec 9, 2011
Penalty
Initial $3,750 · Current $0 Reduced
29 CFR 1910.147(c)(6)(i):  The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed.    a. Ineos USA LLC located in Lima, Ohio:  On or about July 14, 2011, the employer did not ensure employees tasked with conducting annual audits of the company's lockout program, determined if field verifications were being performed with all authorized employees.    The company's lockout program states unit operators must field verify lockout points with all authorized employees working on the equipment before the authorized employee can place a lockout lock on the group lockout board.  The operator's working in the purification section did not field verify with each authorized employee, the lockout points on the spare steam reboiler prior to the authorized employees applying lockout devices to the lockout board.      In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3750

View Ineos USA LLC's full OSHA safety record →