Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: KEYNES BROTHERS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of KEYNES BROTHERS, INC. in 12574 ST. RT. 47 NW, JEFFERSONVILLE, OH 43128 (NAICS 424510). OSHA activity number 331074005.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Keynes Brothers, INC. — free Get an email when a new federal OSHA severe-injury report for Keynes Brothers, INC. is published. One employer, no account, unsubscribe in one click.
Site address
12574 ST. RT. 47 NW
City
JEFFERSONVILLE
State
OH
ZIP
43128
Mailing
12574 ST. RT. 47 NW, JEFFERSONVILLE, OH 43128
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424510
Employees
4
Ownership type
A

3 citations on file for this inspection.

1910.307 C

Serious Gravity 5 2 instances 1 exposed
Issued
Oct 27, 2011
Penalty
Initial $2,040 · Current $1,010 Reduced
29 CFR 1910.307(c):     Electrical installations. Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location. Requirements for each of these options are as follows:    a) In the elevator, the junction box for the globe light had an opening, negating its approved for a class two(II) location.  b) In the tripler area, the globe was missing from the globe light negating its approved for class two(II) loaction.
Recent events (2)
  • — I (S) $1010
  • — Z (S) $2040

1910.110 H06 II B

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 27, 2011
Abate by
Dec 12, 2011
Penalty
Initial $2,040 · Current $1,010 Reduced
29 CFR 1910.110(h)(6)(ii)(b):     Containers shall be protected by crash rails or guards to prevent physical damage unless they are so protected by virtue of their location. Vehicles shall not be serviced within 10 feet of containers.    a) Propane fueling tank located outside of the maintenance shop adjacent to a designated employee parking lot was not  protected by rails or guards to prevent it being struck or damaged by vehicular traffic.
Recent events (2)
  • — I (S) $1010
  • — Z (S) $2040

1910.334 A02 I

Other-than-serious 1 instance 1 exposed
Issued
Oct 25, 2011
Penalty
Initial $2,040 · Current $500 Reduced
29 CFR 1910.334(a)(2)(i):     Portable cord and plug connected equipment and flexible cord sets (extension cords) shall be visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket).  Cord and plug connected equipment and flexible cord sets (extension cords) which remain connected once they are put in place and are not exposed to damage need not be visually inspected until they are relocated.    a) Bin inspection drop light cord was not inspected before inserting into the bins, in that the grounding prong showed scorching.
Recent events (2)
  • — I (O) $500
  • — Z (S) $2040

View Keynes Brothers, INC.'s full OSHA safety record →