Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. ARMY GARRISON, HAWAII

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. ARMY GARRISON, HAWAII in MAINTENANCE SHOPS SCHOFIELD BARRACKS, SCHOFIELD BARRACKS, HI 96857 (NAICS 928110). OSHA activity number 331076398.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Army Garrison, Hawaii — free Get an email when a new federal OSHA severe-injury report for U.S. Army Garrison, Hawaii is published. One employer, no account, unsubscribe in one click.
Site address
MAINTENANCE SHOPS SCHOFIELD BARRACKS
City
SCHOFIELD BARRACKS
State
HI
ZIP
96857
Mailing
OFFICE OF THE GARRISON COMMANDER; IMPC-HI-ZA 851 WRIGHT AVENUE, WAAF (STOP 107), SCHOFIELD BARRACKS, HI 96857
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
100000
Ownership type
D

13 citations on file for this inspection.

1910.22 D02

Serious Gravity 10 1 instance 5 exposed
Issued
Dec 30, 2011
Abate by
Jan 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.22(d)(2):  It shall be unlawful to place, or cause, or permit to be placed, on any floor or roof of a building or other structure a load greater than that for which such floor or roof is approved by the building official:      a.  Electrical shop, storage mezzanine - The mezzanine was used for storage and had not been rated for carrying capacity potentially exposing employees to bodily harm.
Recent events (1)
  • — Z (S) $0

1910.23 C01 I

Serious Gravity 5 3 instances 10 exposed
Issued
Dec 30, 2011
Abate by
Jan 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.23(c)(1)(i):     Every open-sided floor or platform 4 feet or more above adjacent floor or ground level shall beguarded by a standard railing (or the equivalent as specified in paragraph (e)(3) of this section) on all open sides except where there is entrance toa ramp, stairway, or fixed ladder. The railing shall be provided with a toeboard wherever, beneath the open sides, persons can pass:    a.  HVAC Area of Electrical Shop - There was no standard railing including a toprail, midrail and toeboard provided for an open sided mezzanine storage area more than 12 feet above the concrete floor below potentially exposing employees to bodily injury.    b.  Plumbing Shop - The mezzanine storage area, which was more than 14 feet above the concrete floor below, did not have a toeboard potentially exposing employees who passed below to bodily injury.    c.  Electrical Shop - A mezzanine storage area, which was more than 12 feet above the concrete floor below, did not have a toeboard potentially exposing employees who passed below to bodily injury.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 30, 2011
Abate by
Jan 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2):  Each exit was not clearly visible and marked by a sign reading "Exit":    a.  Electrical Shop, north wall - An exit sign over a door was not illuminated potentially exposing employees to the hazard of smoke inhalation and burns.
Recent events (1)
  • — Z (S) $0

1910.157 C01

Serious Gravity 5 4 instances 40 exposed
Issued
Dec 30, 2011
Abate by
Dec 31, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1):  Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:    a.  Sheet Metal  Shop - Three fire extinguishers were not mounted and were blocked potentially exposing employees to smoke inhalation and burns.    b.Welding Shop - A fire extinguisher was not mounted and was blocked potentially exposing employees to smoke inhalation and burns.    c.  Wood Working Shop - Fire extinguishers and an emergency pull were blocked by storage potentially exposing employees to smoke inhalation and burns.    d.  Vehicle Maintenance  Shop- Emergency pull and fire extinguishers were not mounted and were blocked potentially exposing employees to smoke inhalation and burns.
Recent events (1)
  • — Z (S) $0

1910.157 E02

Serious Gravity 5 4 instances 10 exposed
Issued
Dec 30, 2011
Abate by
Jan 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2):     Portable extinguishers or hose used in lieu thereof under paragraph (d)(3) of this section shall be visually inspected monthly.    The tag was not marked to indicate that portable extinguishers were being inspected monthly potentially exposing employees to smoke inhalation and burns in the following locations:    a.  Sheet Metal Shop  b.  Wood Working Shop  c.  Vehicle Maintenance Shop  d.  Plumbing Shop
Recent events (1)
  • — Z (S) $0

1910.176 B

Serious Gravity 5 2 instances 15 exposed
Issued
Dec 30, 2011
Abate by
Jan 4, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.176(b):  Storage of material shall not create a hazard:      a.  HVAC Maintenance, underneath stairway - 15 small propane cylinders, one large propane cylinder, one medium propane cylinder and 1 small cylinder of diclorodibromodifluromethane were unsecured while not in use potentially exposing employees to bodily injury.    b.  Vehicle Maintenance shop - Five small cylinders of freon were not secured while in storage, potentially exposing employees to bodily injury.
Recent events (1)
  • — Z (S) $0

1910.215 B09

Serious Gravity 5 2 instances 10 exposed
Issued
Dec 30, 2011
Abate by
Jan 9, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9):  The distance between the abrasive wheel periphery and the adjustable tongue or the end of theperipheral member at the top shall never exceed one-fourth inc:h:      a.  Wood Working Shop - The DeWalt bench grinder, Model No. DW758, S/N 200223-YI 241, had a tongue guard that was one half inch away from the edge of the abrasive wheel potentially exposing employees to the hazard of bodily injury.     Cycle Maintenance Shop - The Dayton 7 inch bench grinder Lot No. 200204, Model No. 4Z908C, had a tongue guard that was three eighths of an    inch away from the edge of the abrasive wheel potentially exposing employees to the hazard of bodily injury.
Recent events (1)
  • — Z (S) $0

1910.217 B04 I

Serious Gravity 5 1 instance 3 exposed
Issued
Dec 30, 2011
Abate by
Jan 9, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.217(b)(4)(i):  Pedal mechanism(s) on mechanical power press(es) full revolution clutches were not protected to prevent unintended operation from falling or moving objects or by accidental stepping onto the pedals:      a.  Sheet Metal Shop -  The Chicago Press Brake had a broken cover on one of the activation pedals potentially exposing the operator of the machine to amputation from accidentally depressing the pedal.
Recent events (1)
  • — Z (S) $0

1910.304 A02

Serious Gravity 10 1 instance 5 exposed
Issued
Dec 30, 2011
Abate by
Jan 14, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.304(a)(2):  Grounded conductors were attached to terminals or leads so as to reverse designated polarity:    a.  Vehicle Maintenance Shop, Outlet No. CKT17, near emergency shower - A dual receptacle outlet had the polarity reversed potentially exposing employees to electrical shock.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 3 instances 30 exposed
Issued
Dec 30, 2011
Abate by
Jan 19, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A):   Flexible cords and cables were used as a substitute for the fixed wiring of a structure:      a.  Plumbing Shop - Extension cords were used to power lights potentially exposing employees to shock or fire.    b.  Sheet Metal Shop - Extension cords were used to power equipment potentially exposing employees to shock or fire.    c.  Wood Working Shop - Extension cords were used to power a charging station potentially exposing employees to shock or fire.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 30, 2011
Abate by
Jan 19, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D):   Flexible cords and cables were attached to building surfaces:      a.  Wood Working Shop - Extension cords which were used to power a charging station were attached to parts of the building structure potentially exposing employees to shock or fire.
Recent events (1)
  • — Z (S) $0

1904.4

Other-than-serious 3 instances 40 exposed
Issued
Dec 30, 2011
Abate by
Jan 14, 2012
Penalty
Initial $0 · Current $0
29 CFR 1904.4:     Employer did not complete OSHA 300 logs and provide a description of the injury or illness in colum (F).
Recent events (1)
  • — Z (O) $0

1910.151 B

Other-than-serious 15 instances 35 exposed
Issued
Dec 30, 2011
Abate by
Jan 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.151(b):     In the absence of an infirmary, clinic, or hospital in near proximity to the workplace which is used for the treatment of all injured employees, a person or persons shall be adequately trained to render first aid. Adequate first aid supplies shall be readily available.
Recent events (1)
  • — Z (O) $0

View U.S. Army Garrison, Hawaii's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331076398.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.