WILMINGTON, OH ·
OSHA Inspection: BUCKLEY BROS, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BUCKLEY BROS, INC. in 320 EAST MAIN ST., WILMINGTON, OH 45177 (NAICS 424510). OSHA activity number 331080192.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BUCKLEY BROS, INC.
- Site address
- 320 EAST MAIN ST.
- City
- WILMINGTON
- State
- OH
- ZIP
- 45177
- Mailing
- P.O. BOX 845, WILMINGTON, OH 45177
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424510
- Employees
- 18
- Ownership type
- Private (A)
Citations
6 citations on file for this inspection.
1910.146 C05 II C
- Issued
- Nov 4, 2011
- Abate by
- Dec 20, 2011
- Penalty
- Initial $3,570 · Current $2,499 Reduced
General-duty citation text
29 CFR 1910.146(c)(5)(ii)(C): Before an employee enters the space, the internal atmosphere shall be tested, with a calibrated direct-reading instrument, for oxygen content, for flammable gases and vapors, and for potential toxic air contaminants, in that order. Any employee who enters the space, or that employee's authorized representative, shall be provided an opportunity to observe the pre-entry testing required by this paragraph. a) On or about July 21, 2011 space was not tested before entrance to determine the levels within the bin in that employees were entering tanks that had rotting material present which depletes oxygen.
Recent events (2)
- · I (S) $2499
- · Z (S) $3570
1910.219 E03 I
- Issued
- Nov 4, 2011
- Abate by
- Nov 29, 2011
- Penalty
- Initial $2,380 · Current $1,666 Reduced
General-duty citation text
29 CFR 1910.219(e)(3)(i): Vertical and inclined belts shall be enclosed by a guard conforming to standards in paragraphs(m) and (o) of this section. a) Guarding was not provided on the motor drive belt on the Molasses tank exposing employees to pinch points.
Recent events (2)
- · I (S) $1666
- · Z (S) $2380
1910.219 C02 I
- Issued
- Nov 4, 2011
- Abate by
- Nov 29, 2011
- Penalty
- Initial $2,380 · Current $1,666 Reduced
General-duty citation text
29 CFR 1910.219(c)(2)(i): All exposed parts of horizontal shafting seven (7) feet or less from floor or working platform,excepting runways used exclusively for oiling, or running adjustments, shall be protected by a stationary casing enclosing shafting completely or by atrough enclosing sides and top or sides and bottom of shafting as location requires. a) Feed mixer conveyer shaft was not guarded to prevent employees exposure to rotating parts.
Recent events (2)
- · I (S) $1666
- · Z (S) $2380
1910.307 C
- Issued
- Nov 4, 2011
- Abate by
- Feb 13, 2012
- Penalty
- Initial $2,975 · Current $2,083 Reduced
General-duty citation text
29 CFR 1910.307(c): Electrical installations. Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location. Requirements for each of these options are as follows: a) The bin inspection droplight was not intrinsically safe, negating its approved for a class two(II) location. b) The electrical disconect box in the basement was not intrinsically safe, negating its approved for a class two(II) location. c) The electrical disconect box in the basement had two receptical that was not intrinsically safe, in that the recepticals were not encloed, negating its aproved for a class(II) location
Recent events (3)
- · I (S) $2082.5
- · A (S) $2975
- · Z (S) $2975
1910.334 A02 I
- Issued
- Nov 4, 2011
- Penalty
- Initial $1,785 · Current $1,250 Reduced
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) shall be visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket). Cord and plug connected equipment and flexible cord sets (extension cords) which remain connected once they are put in place and are not exposed to damage need not be visually inspected until they are relocated. a) Bin inspection drop light cord was not inspected before inserting into the bins, in that the grounding prong was mising.
Recent events (2)
- · I (S) $1249.5
- · Z (S) $1785
1910.305 B01 II
- Issued
- Nov 4, 2011
- Penalty
- Initial $1,785 · Current $1,250 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. a) Knockout covers were missing from the warehouse main power panel for the lights.
Recent events (2)
- · I (S) $1249.5
- · Z (S) $1785
More inspections at Buckley Bros, INC.
View Buckley Bros, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 424510)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 331080192.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.