OSHA Inspection: FLEET READINESS CENTER

Follow-up inspection · Safety discipline

On , OSHA opened a follow-up safety inspection of FLEET READINESS CENTER in BUILDING 466, CORONADO, CA 92135 (NAICS 811310). OSHA activity number 331098202.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Fleet Readiness Center for free Get an email when a new federal OSHA severe-injury report for Fleet Readiness Center is published. One employer, no account, unsubscribe in one click.
Site address
BUILDING 466
City
CORONADO
State
CA
ZIP
92135
Mailing
BUILDING 466, CORONADO, CA 92135
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811310
Employees
500
Ownership type
D

6 citations on file for this inspection.

1910.157 E02

Serious Gravity 5 4 instances 500 exposed
Issued
May 17, 2012
Abate by
Jun 8, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2):     Portable fire extinguishers were not visually inspected at least monthly:    a) Bldg. 94, mezzanine, column F35 - On or about 4/10/12, a fire extinguisher missed its monthly visual inspection in January and March 2012.    b) Bldg. 94, mezzanine, adjacent to electrical panel 7-14-LP-2-14 - On or about 4/10/12, a fire extinguisher missed its monthly visual inspection in January and March 2012.    c) Bldg. 94, first floor, in hallway outside of supervisor's office - On or about 4/10/12, a fire extinguisher missed its monthly visual inspection in March 2012.    d) Bldg. 94, mezzanine, in hallway outside of FISC office - On or about 4/10/12, a fire extinguisher missed its monthly visual inspection in January and March 2012.
Recent events (1)
  • · Z (S) $0

1910.303 B01

Serious Gravity 5 1 instance 12 exposed
Issued
May 17, 2012
Abate by
Jun 8, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(1):     Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees, in that the employer did not ensure the safety of the equipment pursuant to the considerations in sections (i) through (viii) of 29 CR 1910.303(b)(1):    a) At Bldg. 466, lunchroom, below bulletin boards - On or about 12/6/11, an electrical outlet servicing a snack dispensing machine was not covered to prevent inadvertent contact with exposed 120VAC electrical service wiring.
Recent events (1)
  • · Z (S) $0

1910.334 A01

Serious Gravity 5 1 instance 49 exposed
Issued
May 17, 2012
Abate by
Jun 8, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(1):     Flexible electric cords were fastened with staples or otherwise hung in such a fashion as could damage the outer jacket or insulation:    (a) At Bldg. 94, sheet metal work area adjacent to South men's restroom - On or about 2/16/12, a pendant electrical outlet's cord was tied in a knot so that the insulation was damaged.
Recent events (1)
  • · Z (S) $0

1910.94 B05 IV

Repeat Gravity 10 1 instance 221 exposed
Issued
May 17, 2012
Abate by
Jun 8, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.94(b)(5)(iv):     Portable grinding operations were conducted within a partial enclosure where an average face air velocity was less than 200 feet per minute:    a) At Bldg. 94, Quickie shop Dustron grind booth 039809 - On or about 2/16/12, and a times prior thereto, portable grinding operations were conducted inside the booth where the average face air velocity was below 200 fpm.
Recent events (1)
  • · Z (R) $0

1910.303 G01

Repeat Gravity 5 3 instances 500 exposed
Issued
May 17, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1):     Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    a) At Bldg. 94, adjacent to stairs - On or about 12/6/11, a pallet jack was stored in the area in front of 115V switch boxes and blocked access to switch boxes L4.1, L4.2, L4.3, L4.4, L4.12 and L4.13.    b) At Bldg. 94, adjacent to stairs - On or about 12/6/11, the area in front of a 115V electrical panel labeled 7-6-LP-1-6(NW) was used to store an electric fan.    c) At Bldg. 94, Quickie shop, adjacent to south Lunchroom - On or about 12/7/11, the area in front of a 115V electrical panel was used to store an electric fan.    d) At Bldg. 94, Electrical panels 440 MA3-13 and MA3-14 - On or about 12/7/11, the area in front of four electrical panels were used to store a rolling cart with equipment.    e) At Bldg. 94, first floor, in hallway outside of supervisor's office - On or about 4/10/12, access to a switch box was blocked by an electric cart.
Recent events (1)
  • · Z (R) $0

1910.303 G02 I B

Serious Gravity 5 2 instances 500 exposed
Issued
May 17, 2012
Abate by
Jun 8, 2012
Penalty
Initial $0 · Current $0
1910.303(g)(2)(i)(B):    Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or by suitable permanent, substantial partitions or screens so arranged that only qualified persons will have access to the space within reach of the live parts:     a) Bldg. 466, lunch room, NMCI electrical panel between refrigerator and server - On or about 12/6/11, an electrical panel did not a have panel cover so that the panel could not be locked and was accessible to non-qualified personnel.    b) Bldg. 94, Electrical panels 440 MA3-13, MA3-14, MA3-17, MA3-18, MA3-19, MA3-20 - On or about 12/7/11, the 440 V electrical panel covers had latches but could not be locked. In addition, panel MA3-17 latch cover was missing. Live parts were accessible to non-qualified personnel.
Recent events (1)
  • · Z (S) $0

View Fleet Readiness Center's full OSHA safety record →