OSHA Inspection: DOOR COUNTY COOPERATIVE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DOOR COUNTY COOPERATIVE in 3809 SHIRLEY RD, DE PERE, WI 54115 (NAICS 115114). OSHA activity number 331098491.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Door County Cooperative — free Get an email when a new federal OSHA severe-injury report for Door County Cooperative is published. One employer, no account, unsubscribe in one click.
Site address
3809 SHIRLEY RD
City
DE PERE
State
WI
ZIP
54115
Mailing
317 GREEN BAY RD, STURGEON BAY, WI 54235
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
115114
Employees
8
Ownership type
A

17 citations on file for this inspection.

1910.215 A04

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 23, 2012
Abate by
Apr 30, 2012
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.215(a)(4):     Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:      On 12-05-11, a Daytona 7500L dual wheel bench grinder used in the garage maintenance shop with the machine's left wheel work rest installed greater than one half inch from the wheel.      Abatement Certification or Abatement Documentation required
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.215 B09

Serious Gravity 5 2 instances 2 exposed
Issued
Apr 23, 2012
Abate by
Apr 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9):     The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:      a)  On 12-05-11, a Daytona 7500L dual wheel bench grinder in the garage maintenance shop with the machine's left wheel top guard greater than one inch from the abrasive wheel.    b)  On 12-05-11, a Daytona 7500L dual wheel bench grinder in the garage maintenance shop with the machine's right wheel top guard greater than five-eights (5/8) inch from the abrasive wheel.      Abatement Certification or Abatement Documentation required
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.219 F03

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.219(f)(3):     Sprocket wheels and chains which were seven -7 feet or less above floors or platforms were not enclosed:    On 12-05-11, the chain/sprocket guard installed on the Baldor Motor at Bin 7 outside at a height less than four (4) feet above surface level did not fully enclose the chain and sprocket.        Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.219 D01

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.219(d)(1):     Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):    On 12-05-11, employer did not have the top area of a pulley completely guarded on the Blador Motor at Bin #7 which was outside and less than four (4) feet above surface level.      Abatement Certification or Abatement Documentation required
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.219 E01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.219(e)(1)(i):     Horizontal belts which had both runs 42 inches or less from the floor level were not fully enclosed by guards conforming to requirements specified in 29 CFR 1910.219(m) and (o):      On 12-05-11, employer did not have an adequate guard for the belt on the Baldor Motor at Bin #7 which was outside and less than four (4) feet above surface level.      Abatement Certification or Abatement Documentation required
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B07 I

Serious Gravity 1 1 instance 2 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $2,100 · Current $1,470 Reduced
29 CFR 1910.303(b)(7)(i):     Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment      On 12-05-11, the lighting circuit breaker box located in the garage maintenance shop had an unused opening with exposed conductors in the box.    Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (S) $1470
  • — Z (S) $2100

1910.303 B07 IV

Serious Gravity 1 4 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(iv):     There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating      a)  On 12-05-11, there was broken conduit on the conductors between the electrical enclosure mounted on Bin #2 and the Sukup auger motor at the FS site.    b)  On 12-05-11, there was broken conduit on the conductors between the electrical enclosure mounted on Bin #4 and the Vaunguard motor at the FS site.    c)  On 12-05-11, there was broken conduit on the conductors between the compacted surface level and Bin #6 blower electrical control at the FS site.      Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 VII B

Serious Gravity 5 3 instances 4 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $3,500 · Current $2,450 Reduced
29 CFR 1910.303(g)(1)(vii)(B):     Outdoor electrical equipment was not installed in suitable enclosures and protected by accidental contact by unauthorized personnel:      a)  On 12-05-11, four sets of on/off button boxes, fuses, and exposed live parts inside a Hoffman electrical enclosure located outside and mounted to the side of a bin less than six feet above surface level at the FS site without a door latch or lock; the enclosure door was secured with a bungee strap.      Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (S) $2450
  • — Z (S) $3500

1910.303 G02 I

Serious 3 instances 4 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i):     Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):      a)  On 12-05-11, a three Pole 480V circuit Breaker, fuses, and exposed live parts inside a Hoffman electrical enclosure located in the Drop-Pit Drive-Through building mounted on a wall less than six feet above surface level without a door latch or lock.    b)  On 12-05-11, five switches, temporary wiring, and exposed live parts inside a Furnas electrical enclosure located in the Drop-Pit Drive-Through building mounted on a wall less than six feet above surface level without a door latch or lock.     c)  On 12-05-11, four sets of on/off button boxes, fuses, and exposed live parts inside a Hoffman electrical enclosure located outside and mounted to the side of a bin less than six feet above surface level at the FS site without a door latch or lock; the enclosure door was secured with a bungee strap.      Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 I

Serious Gravity 10 3 instances 4 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $4,900 · Current $3,430 Reduced
29 CFR 1910.305(b)(1)(i):     Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:      a)  On 12-05-11, two flexible cables had been installed as temporary wiring without any abrasion protection through a Furnas enclosure bottom panel located in the Drop-Pit Drive-Through building.    b)  On 12-05-11, a flexible cable on a Sukup fan was installed without abrasion protection located outside at bin #6 on the store site.     c)  On 12-05-11, a flexible cable was installed without any abrasion protection between the electrical feed box and the lighting circuit breaker switch box located in the garage maintenance shop.      Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (S) $3430
  • — Z (S) $4900

1910.305 F

Serious Gravity 10 1 instance 4 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(f):     The conductor insulation was not approved for the voltage, operating temperature, and/or location of use:      On 12-05-11, Romex indoor use flexible cord was installed as temporary wiring with feed from the electrical switch box located in the Drop-Pit Drive-through building and running outside to the bin fan motors.      Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 10 1 instance 4 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B):     Flexible cords and cables were run through holes in walls, ceilings, or floors:      On 12-05-11, the employer had three flexible cables, two black and one yellow Romex, as temporary wiring running from a Furnas electrical enclosure through the Drop-Pit Drive-Through building wall to the fans outside.      Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 3 instances 4 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii):     Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:      a)  On 12-05-11, the employer had temporary wiring, yellow Romex, installed out from a hole in the bottom panel of the Furnas electrical enclosure located in the Drop-Pit Drive-Through building without any strain relief.    b)  On 12-05-11, the employer had temporary wiring, black cable, installed out from a hole in the bottom panel of the Furnas electrical enclosure located in the Drop-Pit Drive-Through building without any strain relief.    c)  On 12-05-11, the employer had a Sukup fan located at Bin #6 installed without strain relief.        Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Other-than-serious 1 instance 4 exposed
Issued
Apr 23, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):     Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:      On 12-05-11, employees were utilizing the lighting circuit breaker switches as the on and off switches for the garage maintenance shop.      Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 E01 II

Other-than-serious 3 instances 4 exposed
Issued
Apr 23, 2012
Abate by
Apr 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(e)(1)(ii):     Electrical equipment did not have markings giving voltage, current, wattage, or other ratings as necessary:      a)  On 12-05-11, the Hoffman electrical enclosure located next to the vehicle exit door in the Drop-Pit Drive-Through building was not labeled with voltage, current, and wattage.    b)  On 12-05-11, the Furnas electrical enclosure located in the vehicle exit area in the Drop-Pit Drive-Through building was not labeled with voltage, current, and wattage.    c)  On 12-05-11, the Hoffman electrical enclosure mounted on the side of a bin on the FS site was not labeled with voltage, current, and wattage.      Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 F02

Other-than-serious 3 instances 4 exposed
Issued
Apr 23, 2012
Abate by
Apr 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2):     Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:      a)  On 12-05-11, the employer did not have markings to identify the purpose of switches installed in the Hoffman electrical enclosure located next to the vehicle exit door in the Drop-Pit Drive-Through building at the main site.    b)  On 12-05-11, the employer did not have markings to identify the purpose of switches installed in the Furnas electrical enclosure located in the vehicle exit area in the Drop-Pit Drive-Through building at the main site.    c)  On 12-05-11, the employer did not have markings to identify the purpose of switches installed in the Hoffman electrical enclosure mounted on the side of a bin outside at the FS site.      Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 2 instances 4 exposed
Issued
Apr 23, 2012
Abate by
Apr 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii):     The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:      a)  On 12-05-11, an employee had a twelve foot, non-self-supporting, portable metal ladder stored against the front of an electrical switch box in the Drop Pit Drive-Through building.    b)  On 12-05-11, the employer had a Square D electrical box which had feed hooked up to an Ingersoll Rand compressor blocked with various stored items and debris in the back work shop in the maintenance garage.      Abatement Certification or Abatement Documentation is required
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Door County Cooperative's full OSHA safety record →