ANDERSON, CA —
OSHA Inspection: BUREAU OF RECLAMATION
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of BUREAU OF RECLAMATION in 24411 COLEMAN FISH HATCHERY ROAD, ANDERSON, CA 96007 (NAICS 811310). OSHA activity number 331110437.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BUREAU OF RECLAMATION
- Site address
- 24411 COLEMAN FISH HATCHERY ROAD
- City
- ANDERSON
- State
- CA
- ZIP
- 96007
- Mailing
- 16349 SHASTA DAM BOULVEVARD, SHASTA LAKE, CA 96019
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811310
- Employees
- 165
- Ownership type
- D
Citations
6 citations on file for this inspection.
1910.333 A01
- Issued
- Mar 19, 2012
- Abate by
- Mar 22, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(a)(1): "Deenergized parts." Live parts to which an employee may be exposed was not deenergized before the employee works on or near them, and the employer did not demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. a.) Chiller Building, Coleman National Fish Hatchery - On or about November 04, 2012 and at times prior thereto, the 480 volt electrical panel was not deenergized prior to an employee working on the equipment.
Recent events (1)
- — Z (S) $0
1910.333 A02
- Issued
- Mar 19, 2012
- Abate by
- Mar 28, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(a)(2): Where exposed live parts were not deenergized, other safety related work practices were not used to protect employees who could be exposed to the electrical hazards involved: a) Coleman National Fish Hatchery, Chiller Building- On or about November 04, 2011 and at time prior thereto, the employee did not deenergize the 480 volt electrical panel. The employer did not ensure the employee used safe work related practices such as lock out/tag out procedures.
Recent events (1)
- — Z (S) $0
1910.335 A01 IV
- Issued
- Mar 19, 2012
- Abate by
- Mar 26, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(iv): Employees did not wear nonconductive head protection wherever there is a danger of head injury from electric shock or burns due to contact with exposed energized parts. a) Coleman National Fish Hatchery, Chiller Building- On or about November 04,2011 and at times prior thereto, the employer did not ensure the employee was wearing or was provided nonconductive head protection.
Recent events (1)
- — Z (S) $0
1910.335 A01 V
- Issued
- Mar 19, 2012
- Abate by
- Mar 26, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(v): Employees shall wear protective equipment for the eyes or face wherever there is danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion. a) Coleman National Fish Hatchery, Chiller Building- On or about Novemeber 04, 2011and at times prior thereto, the employee was not wearing protective equipment for the eyes and face when he was working on the energized 480 volt electrical panel.
Recent events (1)
- — Z (S) $0
1910.335 A02 II
- Issued
- Mar 19, 2012
- Abate by
- Mar 22, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(2)(ii): Protective shields, protective barriers, or insulating materials were not used to protect each employee from shock, burns, or other electrically related injuries while that employee was working near exposed energized parts which might be accidentally contacted or where dangerous electric heating or arcing might occur. a) Coleman National Fish Hatchery, Chiller Building- On or about November 04, 2011 and at times thereto, the employer did not provided protective shields, protective barriers or insulating materials (flame resistent clothing) to protect the employee while he was working on an energized 480 volt electrical panel.
Recent events (1)
- — Z (S) $0
1910.335 B01
- Issued
- Mar 19, 2012
- Abate by
- Mar 28, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(b)(1): Safety signs and tags. Safety signs, safety symbols, or accident prevention tags were not used where necessary to warn employees about electrical hazards which may endanger them, as required by 1910.145. a.) Coleman National Fish Hatchery, Chiller Building - On or about November 04, 2011 and at times prior thereto, the 480 volt electrical panel did not have a sign or symbol warning employees regarding arc flash.
Recent events (1)
- — Z (S) $0
More inspections at Bureau of Reclamation
View Bureau of Reclamation's full OSHA safety record →
More inspections in this industry (NAICS 811310)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331110437.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.