IDAHO FALLS, ID —
OSHA Inspection: SWIRE PACIFIC HOLDINGS INC. DBA SWIRE COCA-COLA, USA
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of SWIRE PACIFIC HOLDINGS INC. DBA SWIRE COCA-COLA, USA in 900 E. LINCOLN, IDAHO FALLS, ID 83401 (NAICS 424490). OSHA activity number 331907774.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SWIRE PACIFIC HOLDINGS INC. DBA SWIRE COCA-COLA, USA
- Site address
- 900 E. LINCOLN
- City
- IDAHO FALLS
- State
- ID
- ZIP
- 83401
- Mailing
- 900 E. LINCOLN, IDAHO FALLS, ID 83401
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424490
- Employees
- 40
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.23 C01
- Issued
- Jul 9, 2012
- Abate by
- Aug 3, 2012
- Penalty
- Initial $2,700 · Current $1,900 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Every open-sided floor or platform 4 feet or more above adjacent floor or ground level was not guarded by a standard railing (or the equivalent as specified in paragraph (e)(3) of this section) on all open sides: (a) On the mezzanine: On or about January 31, 2012, and at times prior thereto, employees accessing the storage space on the mezzanine were not protected by a standard guard rail. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $1900
- — Z (S) $2700
1910.219 F03
- Issued
- Jul 9, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $2,025 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.219(f)(3): Sprocket wheels and chains which were seven (7) feet or less above floors or platforms were not enclosed: (a) Near the ice machine: On or about January 31, 2012, and at times prior thereto, the bottom chain and sprocket for the ice conveyer was not guarded. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $1400
- — Z (S) $2025
1910.303 G01 II
- Issued
- Jul 9, 2012
- Abate by
- Jul 16, 2012
- Penalty
- Initial $2,025 · Current $1,425 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: (a) In the Special Events Room: On or about January 31, 2012, and at times prior thereto, access to the breaker panels in the room was blocked by equipment. (b) Outside the Service Department: On or about January 31, 2012, and at times prior thereto, equipment and material were stored in front of the breaker panels on the wall outside the room. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $1425
- — Z (S) $2025
1910.305 B01 II
- Issued
- Jul 9, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) Special Events Room: On or about January 31, 2012, and at times prior thereto, a knockout was missing from breaker panel "P1". (b) Southwest wall: On or about January 31, 2012, and at times prior thereto, a knockout was missing from the panel in the wall. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Jul 9, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: (a) Special Events Room: On or about January 31, 2012, and at times prior thereto, a junction box above panel "P1" did not have a cover. (b) Service Department: On or about January 31, 2012, and at times prior thereto, a junction box on the east wall did not have a cover on it. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jul 9, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) Near the ice machine: On or about January 31, 2012, and at times prior thereto, the ice machine was plugged into an extension cord instead of directly into an receptacle. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Jul 9, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors: (a) Near the ice machine: On or about January 31, 2012, and at times prior thereto, an extension cord was run through a hole in the wall behind the ice machine. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Jul 9, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and/or cables were run through doorways, windows, or similar openings: (a) Near the ice machine: On or about January 31, 2012, and at times prior thereto, the extension cord used to power the ice machine was run through an open doorway. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J01 I
- Issued
- Jul 9, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact: (a) Front entrance: On or about January 31, 2012, and at times prior thereto, the receptacle in the main entrance did not have a cover. (b) Near the ice machine: On or about January 31, 2012 and at times prior thereo, the cover was falling off the receptacle next to the ice machine. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 B02
- Issued
- Jul 9, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": (a) Loading Dock: On or about January 31, 2012, and at times prior thereto, the exit was not marked by an exit sign. Note: Abatement certificaiton is required for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.157 E02
- Issued
- Jul 9, 2012
- Abate by
- Jul 16, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: (a) Throughout the facility: On or about January 31, 2012, and at times prior thereto, the fire extinguishers in the facility had not been visually inspected on a monthly basis. Note: Abatement certification is required for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Swire Pacific Holdings INC. DBA Swire Coca-Cola, USA
View Swire Pacific Holdings INC. DBA Swire Coca-Cola, USA's full OSHA safety record →
More inspections in this industry (NAICS 424490)
More inspections in ID
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331907774.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.