Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. AIR FORCE 60TH CIVIL ENGINEERING SQUADRON

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of U.S. AIR FORCE 60TH CIVIL ENGINEERING SQUADRON in 241 V STREET BLDG. 878, TRAVIS AFB, CA 94535 (NAICS 928110). OSHA activity number 331917591.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. AIR Force 60TH Civil Engineering Squadron — free Get an email when a new federal OSHA severe-injury report for U.S. AIR Force 60TH Civil Engineering Squadron is published. One employer, no account, unsubscribe in one click.
Site address
241 V STREET BLDG. 878
City
TRAVIS AFB
State
CA
ZIP
94535
Mailing
411 AIRMAN DRIVE, TRAVIS AFB, CA 94535
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
72
Ownership type
D

4 citations on file for this inspection.

1910.37 A01

Serious Gravity 5 1 instance 4 exposed
Issued
Jul 30, 2012
Abate by
Aug 20, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(1): Exit routes must be kept free of explosive or highly flammable furnishings or other decorations:      a.   Bldg. 872, Airfield Shed - Noted on or about 2/15/12, acetylene cylinders were stored in the cylinder cage adjacent to the exit door partially blocking it.
Recent events (1)
  • — Z (S) $0

1910.37 A03

Serious Gravity 5 1 instance 4 exposed
Issued
Jul 30, 2012
Abate by
Aug 20, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Materials or equipment were placed, either permanently or temporarily, within the exit route:      a.   Bldg. 872, Airfield Shed - Noted on or about 2/15/12, acetylene cylinders were stored in the cylinder cage adjacent to the exit door partially blocking it.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Jul 30, 2012
Abate by
Aug 20, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit must be clearly visible and marked by a sign reading "Exit":      a.  Bldg. 872, Airfield Shed - Noted on or about 2/15/12, the exit door adjacent  to the cylinder storage cage did not have an exit sign posted.
Recent events (1)
  • — Z (S) $0

1910.253 B04 III

Serious Gravity 5 1 instance 4 exposed
Issued
Jul 30, 2012
Abate by
Aug 20, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:      a.  Bldg. 872, Airfield Shed -  Noted on or about 2/15/12,  a cylinder storage cage containing acetylene and propane cylinders were stored 16',10" away from another cylinder cage containing oxygen cylinders.
Recent events (1)
  • — Z (S) $0

View U.S. AIR Force 60TH Civil Engineering Squadron's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331917591.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.