TRAVIS AFB, CA —
OSHA Inspection: U.S. AIR FORCE 60TH CIVIL ENGINEERING SQUADRON
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of U.S. AIR FORCE 60TH CIVIL ENGINEERING SQUADRON in 241 V STREET BLDG. 878, TRAVIS AFB, CA 94535 (NAICS 928110). OSHA activity number 331917591.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. AIR FORCE 60TH CIVIL ENGINEERING SQUADRON
- Site address
- 241 V STREET BLDG. 878
- City
- TRAVIS AFB
- State
- CA
- ZIP
- 94535
- Mailing
- 411 AIRMAN DRIVE, TRAVIS AFB, CA 94535
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 72
- Ownership type
- D
Citations
4 citations on file for this inspection.
1910.37 A01
- Issued
- Jul 30, 2012
- Abate by
- Aug 20, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(1): Exit routes must be kept free of explosive or highly flammable furnishings or other decorations: a. Bldg. 872, Airfield Shed - Noted on or about 2/15/12, acetylene cylinders were stored in the cylinder cage adjacent to the exit door partially blocking it.
Recent events (1)
- — Z (S) $0
1910.37 A03
- Issued
- Jul 30, 2012
- Abate by
- Aug 20, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Materials or equipment were placed, either permanently or temporarily, within the exit route: a. Bldg. 872, Airfield Shed - Noted on or about 2/15/12, acetylene cylinders were stored in the cylinder cage adjacent to the exit door partially blocking it.
Recent events (1)
- — Z (S) $0
1910.37 B02
- Issued
- Jul 30, 2012
- Abate by
- Aug 20, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit must be clearly visible and marked by a sign reading "Exit": a. Bldg. 872, Airfield Shed - Noted on or about 2/15/12, the exit door adjacent to the cylinder storage cage did not have an exit sign posted.
Recent events (1)
- — Z (S) $0
1910.253 B04 III
- Issued
- Jul 30, 2012
- Abate by
- Aug 20, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: a. Bldg. 872, Airfield Shed - Noted on or about 2/15/12, a cylinder storage cage containing acetylene and propane cylinders were stored 16',10" away from another cylinder cage containing oxygen cylinders.
Recent events (1)
- — Z (S) $0
More inspections at U.S. AIR Force 60TH Civil Engineering Squadron
View U.S. AIR Force 60TH Civil Engineering Squadron's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331917591.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.